Cleveland Cables Cable Calculator

Cable Cross-Sectional Area Formula:

\[ A = \frac{2 \times \rho \times L \times I}{V_D} \]

ohm-m
meters
amps
volts

Unit Converter ▲

Unit Converter ▼

From: To:

1. What is the Cleveland Cables Cable Calculator?

Definition: This calculator determines the required cross-sectional area of a cable based on resistivity, length, current, and acceptable voltage drop.

Purpose: It helps electricians and engineers select the proper cable size for electrical installations to ensure safe and efficient power transmission.

2. How Does the Calculator Work?

The calculator uses the formula:

\[ A = \frac{2 \times \rho \times L \times I}{V_D} \]

Where:

Explanation: The formula calculates the minimum conductor size needed to maintain the voltage drop within acceptable limits for a given current over a specified cable length.

3. Importance of Proper Cable Sizing

Details: Correct cable sizing prevents excessive voltage drop (which can affect equipment performance), reduces energy loss, and minimizes heat generation for safety.

4. Using the Calculator

Tips:

5. Frequently Asked Questions (FAQ)

Q1: Why is the resistivity value important?
A: Different materials have different resistivities, which significantly affect the required cable size for the same current and length.

Q2: What's a typical voltage drop allowance?
A: Most electrical codes recommend no more than 3-5% voltage drop from source to load.

Q3: Why multiply by 2 in the formula?
A: The factor of 2 accounts for the return path in single-phase AC or DC circuits.

Q4: How do I convert the result to mm²?
A: Multiply the result in m² by 1,000,000 to get mm² (1 m² = 1,000,000 mm²).

Q5: Does this account for temperature effects?
A: No, for high-temperature applications, you may need to adjust the resistivity value.