Voltage Drop Calculator

Voltage drop calculator

Enter the circuit and press the button. You get the volts lost in the wire, the percent drop, the voltage left at the load and, if the run is too long, the wire size that brings it back under your target.

V
A
One way, from the source to the load.
°C
%
75 °C is the NEC basis for loaded building wire. Use 20 °C for room temperature. 3% is the NEC guideline for one circuit.

Voltage drop

Fill in the circuit, then press the button.

How the calculator works

VD = 2 × R × L × I ÷ 1,000

VD = 1.732 × R × L × I ÷ 1,000

R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.

Resistance comes from the 75 °C column of NEC Chapter 9, Table 8 for stranded conductors, the same basis Southwire and most electrical engineers use for a quick check. On AC runs of 1/0 and larger, inductive reactance adds a little more drop, so leave some margin there.

How far can common circuits run?

The longest one-way distance on copper before the drop reaches 3% and 5%, with each circuit loaded to 80% of its breaker. Past these lengths, go up one wire size.

CircuitWire3% limit5% limit
15 A lighting, 120 V14 AWG47 ft79 ft
20 A receptacles, 120 V12 AWG56 ft94 ft
30 A dryer, 240 V10 AWG120 ft201 ft
50 A range, 240 V6 AWG183 ft305 ft
60 A subpanel, 240 V6 AWG152 ft254 ft
100 A feeder, 240 V3 AWG183 ft306 ft

Copper, Table 8 resistance at 75 °C. Load at 80% of the breaker rating.

What drop is acceptable?

The NEC suggests no more than 3% on a branch circuit or feeder and 5% from the service to the farthest outlet. These figures sit in informational notes, so they are advice rather than law, but inspectors, engineers and equipment makers lean on them. Motors run hotter, LED drivers flicker and heaters lose output when voltage sags further.

  • 120 V: 3% is 3.6 V, 5% is 6 V
  • 240 V: 3% is 7.2 V, 5% is 12 V
  • 208 V: 3% is 6.2 V, 5% is 10.4 V
  • 480 V: 3% is 14.4 V, 5% is 24 V
  • 12 V DC: 3% is 0.36 V, 10% is 1.2 V

More on the limits: acceptable voltage drop and NEC voltage drop rules.

Resistivity of conductor materials

For copper and aluminum in the standard building sizes, the calculator uses NEC Table 8. For other metals and for odd or fine gauges it works from resistivity and the wire's cross-section, R = ρ × L ÷ A, then corrects for temperature.

MaterialResistivity at 20 °CTemperature coefficientRelative to copper
Silver1.59 × 10⁻⁸ Ω·m0.0038 per °C0.92×
Copper1.72 × 10⁻⁸ Ω·m0.0039 per °C1.00×
Gold2.44 × 10⁻⁸ Ω·m0.0034 per °C1.42×
Aluminum2.65 × 10⁻⁸ Ω·m0.0040 per °C1.54×
Tungsten5.60 × 10⁻⁸ Ω·m0.0045 per °C3.26×
Iron9.71 × 10⁻⁸ Ω·m0.0050 per °C5.65×
Platinum10.60 × 10⁻⁸ Ω·m0.0039 per °C6.16×
Steel20.00 × 10⁻⁸ Ω·m0.0030 per °C11.63×

Typical handbook values for the pure metals. Iron and steel vary widely by alloy.

Silver conducts slightly better than copper but costs far more; it is used in plating and contacts. Gold resists corrosion, which is why it plates connectors. Tungsten, platinum, iron and steel are used for heating elements, sensors, fences and ground rods rather than for carrying power.

AWG size, area and resistance

AWGDiameterAreaCopper Ω/km at 20 °CCopper Ω/1,000 ft at 20 °C
4/011.684 mm107.2 mm²0.16040.0489
3/010.405 mm85.03 mm²0.20230.06166
2/09.266 mm67.43 mm²0.25510.07775
1/08.251 mm53.48 mm²0.32160.09804
17.348 mm42.41 mm²0.40560.1236
26.544 mm33.63 mm²0.51140.1559
35.827 mm26.67 mm²0.64490.1966
45.189 mm21.15 mm²0.81320.2479
54.621 mm16.77 mm²1.0250.3126
64.115 mm13.3 mm²1.2930.3941
73.665 mm10.55 mm²1.6310.497
83.264 mm8.366 mm²2.0560.6267
92.906 mm6.634 mm²2.5930.7902
102.588 mm5.261 mm²3.2690.9965
112.305 mm4.172 mm²4.1221.257
122.053 mm3.309 mm²5.1981.584
131.828 mm2.624 mm²6.5551.998
141.628 mm2.081 mm²8.2662.519
151.450 mm1.65 mm²10.423.177
161.291 mm1.309 mm²13.144.006
171.150 mm1.038 mm²16.575.051
181.024 mm0.823 mm²20.96.37
190.912 mm0.6527 mm²26.358.032
200.812 mm0.5176 mm²33.2310.13
210.723 mm0.4105 mm²41.912.77
220.644 mm0.3255 mm²52.8416.1
230.573 mm0.2582 mm²66.6320.31
240.511 mm0.2047 mm²84.0125.61
250.455 mm0.1624 mm²105.932.29
260.405 mm0.1288 mm²133.640.72
270.361 mm0.1021 mm²168.451.34
280.321 mm0.08098 mm²212.464.74
290.286 mm0.06422 mm²267.881.64
300.255 mm0.05093 mm²337.7102.9
310.227 mm0.04039 mm²425.9129.8
320.202 mm0.03203 mm²537163.7
330.180 mm0.0254 mm²677.2206.4
340.160 mm0.02014 mm²853.9260.3
350.143 mm0.01597 mm²1077328.2
360.127 mm0.01267 mm²1358413.9
370.113 mm0.01005 mm²1712521.9
380.101 mm0.007967 mm²2159658.1
390.090 mm0.006318 mm²2722829.8
400.080 mm0.00501 mm²34331046

Solid round wire, from the ASTM B258 gauge formula and copper resistivity of 1.72 × 10⁻⁸ Ω·m.

Older tools

The calculators from the earlier version of this site, including resistor, capacitor, PCB and dB tools, are still online. Browse all older tools.

Common questions

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Is 3% voltage drop a code requirement?

Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.

Why does aluminum need a bigger wire?

Aluminum has about 61% of copper's conductivity, so the same gauge drops about 1.6 times as much voltage. A common swap is two sizes larger in aluminum, for example 4/0 aluminum in place of 2/0 copper.

Does voltage drop change with temperature?

Yes. Resistance rises about 0.32% per °C for copper. The Table 8 values assume 75 °C, a hot conductor carrying a full load, so lightly loaded or cool wires drop slightly less than shown.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
  • https://www.southwire.com/calculator-vdrop
  • ASTM B258, Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires