Voltage drop calculator
Enter the circuit and press the button. You get the volts lost in the wire, the percent drop, the voltage left at the load and, if the run is too long, the wire size that brings it back under your target.
Voltage drop
Fill in the circuit, then press the button.
How the calculator works
VD = 2 × R × L × I ÷ 1,000
VD = 1.732 × R × L × I ÷ 1,000
R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.
Resistance comes from the 75 °C column of NEC Chapter 9, Table 8 for stranded conductors, the same basis Southwire and most electrical engineers use for a quick check. On AC runs of 1/0 and larger, inductive reactance adds a little more drop, so leave some margin there.
How far can common circuits run?
The longest one-way distance on copper before the drop reaches 3% and 5%, with each circuit loaded to 80% of its breaker. Past these lengths, go up one wire size.
| Circuit | Wire | 3% limit | 5% limit |
|---|---|---|---|
| 15 A lighting, 120 V | 14 AWG | 47 ft | 79 ft |
| 20 A receptacles, 120 V | 12 AWG | 56 ft | 94 ft |
| 30 A dryer, 240 V | 10 AWG | 120 ft | 201 ft |
| 50 A range, 240 V | 6 AWG | 183 ft | 305 ft |
| 60 A subpanel, 240 V | 6 AWG | 152 ft | 254 ft |
| 100 A feeder, 240 V | 3 AWG | 183 ft | 306 ft |
Copper, Table 8 resistance at 75 °C. Load at 80% of the breaker rating.
What drop is acceptable?
The NEC suggests no more than 3% on a branch circuit or feeder and 5% from the service to the farthest outlet. These figures sit in informational notes, so they are advice rather than law, but inspectors, engineers and equipment makers lean on them. Motors run hotter, LED drivers flicker and heaters lose output when voltage sags further.
- 120 V: 3% is 3.6 V, 5% is 6 V
- 240 V: 3% is 7.2 V, 5% is 12 V
- 208 V: 3% is 6.2 V, 5% is 10.4 V
- 480 V: 3% is 14.4 V, 5% is 24 V
- 12 V DC: 3% is 0.36 V, 10% is 1.2 V
More on the limits: acceptable voltage drop and NEC voltage drop rules.
Resistivity of conductor materials
For copper and aluminum in the standard building sizes, the calculator uses NEC Table 8. For other metals and for odd or fine gauges it works from resistivity and the wire's cross-section, R = ρ × L ÷ A, then corrects for temperature.
| Material | Resistivity at 20 °C | Temperature coefficient | Relative to copper |
|---|---|---|---|
| Silver | 1.59 × 10⁻⁸ Ω·m | 0.0038 per °C | 0.92× |
| Copper | 1.72 × 10⁻⁸ Ω·m | 0.0039 per °C | 1.00× |
| Gold | 2.44 × 10⁻⁸ Ω·m | 0.0034 per °C | 1.42× |
| Aluminum | 2.65 × 10⁻⁸ Ω·m | 0.0040 per °C | 1.54× |
| Tungsten | 5.60 × 10⁻⁸ Ω·m | 0.0045 per °C | 3.26× |
| Iron | 9.71 × 10⁻⁸ Ω·m | 0.0050 per °C | 5.65× |
| Platinum | 10.60 × 10⁻⁸ Ω·m | 0.0039 per °C | 6.16× |
| Steel | 20.00 × 10⁻⁸ Ω·m | 0.0030 per °C | 11.63× |
Typical handbook values for the pure metals. Iron and steel vary widely by alloy.
Silver conducts slightly better than copper but costs far more; it is used in plating and contacts. Gold resists corrosion, which is why it plates connectors. Tungsten, platinum, iron and steel are used for heating elements, sensors, fences and ground rods rather than for carrying power.
AWG size, area and resistance
| AWG | Diameter | Area | Copper Ω/km at 20 °C | Copper Ω/1,000 ft at 20 °C |
|---|---|---|---|---|
| 4/0 | 11.684 mm | 107.2 mm² | 0.1604 | 0.0489 |
| 3/0 | 10.405 mm | 85.03 mm² | 0.2023 | 0.06166 |
| 2/0 | 9.266 mm | 67.43 mm² | 0.2551 | 0.07775 |
| 1/0 | 8.251 mm | 53.48 mm² | 0.3216 | 0.09804 |
| 1 | 7.348 mm | 42.41 mm² | 0.4056 | 0.1236 |
| 2 | 6.544 mm | 33.63 mm² | 0.5114 | 0.1559 |
| 3 | 5.827 mm | 26.67 mm² | 0.6449 | 0.1966 |
| 4 | 5.189 mm | 21.15 mm² | 0.8132 | 0.2479 |
| 5 | 4.621 mm | 16.77 mm² | 1.025 | 0.3126 |
| 6 | 4.115 mm | 13.3 mm² | 1.293 | 0.3941 |
| 7 | 3.665 mm | 10.55 mm² | 1.631 | 0.497 |
| 8 | 3.264 mm | 8.366 mm² | 2.056 | 0.6267 |
| 9 | 2.906 mm | 6.634 mm² | 2.593 | 0.7902 |
| 10 | 2.588 mm | 5.261 mm² | 3.269 | 0.9965 |
| 11 | 2.305 mm | 4.172 mm² | 4.122 | 1.257 |
| 12 | 2.053 mm | 3.309 mm² | 5.198 | 1.584 |
| 13 | 1.828 mm | 2.624 mm² | 6.555 | 1.998 |
| 14 | 1.628 mm | 2.081 mm² | 8.266 | 2.519 |
| 15 | 1.450 mm | 1.65 mm² | 10.42 | 3.177 |
| 16 | 1.291 mm | 1.309 mm² | 13.14 | 4.006 |
| 17 | 1.150 mm | 1.038 mm² | 16.57 | 5.051 |
| 18 | 1.024 mm | 0.823 mm² | 20.9 | 6.37 |
| 19 | 0.912 mm | 0.6527 mm² | 26.35 | 8.032 |
| 20 | 0.812 mm | 0.5176 mm² | 33.23 | 10.13 |
| 21 | 0.723 mm | 0.4105 mm² | 41.9 | 12.77 |
| 22 | 0.644 mm | 0.3255 mm² | 52.84 | 16.1 |
| 23 | 0.573 mm | 0.2582 mm² | 66.63 | 20.31 |
| 24 | 0.511 mm | 0.2047 mm² | 84.01 | 25.61 |
| 25 | 0.455 mm | 0.1624 mm² | 105.9 | 32.29 |
| 26 | 0.405 mm | 0.1288 mm² | 133.6 | 40.72 |
| 27 | 0.361 mm | 0.1021 mm² | 168.4 | 51.34 |
| 28 | 0.321 mm | 0.08098 mm² | 212.4 | 64.74 |
| 29 | 0.286 mm | 0.06422 mm² | 267.8 | 81.64 |
| 30 | 0.255 mm | 0.05093 mm² | 337.7 | 102.9 |
| 31 | 0.227 mm | 0.04039 mm² | 425.9 | 129.8 |
| 32 | 0.202 mm | 0.03203 mm² | 537 | 163.7 |
| 33 | 0.180 mm | 0.0254 mm² | 677.2 | 206.4 |
| 34 | 0.160 mm | 0.02014 mm² | 853.9 | 260.3 |
| 35 | 0.143 mm | 0.01597 mm² | 1077 | 328.2 |
| 36 | 0.127 mm | 0.01267 mm² | 1358 | 413.9 |
| 37 | 0.113 mm | 0.01005 mm² | 1712 | 521.9 |
| 38 | 0.101 mm | 0.007967 mm² | 2159 | 658.1 |
| 39 | 0.090 mm | 0.006318 mm² | 2722 | 829.8 |
| 40 | 0.080 mm | 0.00501 mm² | 3433 | 1046 |
Solid round wire, from the ASTM B258 gauge formula and copper resistivity of 1.72 × 10⁻⁸ Ω·m.
Older tools
The calculators from the earlier version of this site, including resistor, capacitor, PCB and dB tools, are still online. Browse all older tools.
Common questions
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Is 3% voltage drop a code requirement?
Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.
Why does aluminum need a bigger wire?
Aluminum has about 61% of copper's conductivity, so the same gauge drops about 1.6 times as much voltage. A common swap is two sizes larger in aluminum, for example 4/0 aluminum in place of 2/0 copper.
Does voltage drop change with temperature?
Yes. Resistance rises about 0.32% per °C for copper. The Table 8 values assume 75 °C, a hot conductor carrying a full load, so lightly loaded or cool wires drop slightly less than shown.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
- https://www.southwire.com/calculator-vdrop
- ASTM B258, Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires