Maximum wire distance calculator
Enter the voltage and current to see how far each wire size can run before the drop passes your limit. Choose a size to get one exact figure.
Maximum distance
Fill in the circuit, then press the button.
Distance formula
L = (V × %) × 1,000 ÷ (2 × R × I)
Rearranged from the voltage drop formula. Use 1.732 in place of 2 for three-phase. Double the current and the distance halves; double the voltage and it doubles.
Maximum distance at 120 V, 3%
| Load | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG |
|---|---|---|---|---|---|---|
| 10 A | 57 ft | 90 ft | 145 ft | 231 ft | 366 ft | 584 ft |
| 15 A | 38 ft | 60 ft | 96 ft | 154 ft | 244 ft | 389 ft |
| 20 A | — | 45 ft | 72 ft | 115 ft | 183 ft | 292 ft |
| 30 A | — | — | 48 ft | 77 ft | 122 ft | 194 ft |
Maximum distance at 240 V, 3%
| Load | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 2 AWG | 1/0 AWG |
|---|---|---|---|---|---|---|---|
| 20 A | 90 ft | 145 ft | 231 ft | 366 ft | 584 ft | 927 ft | 1,475 ft |
| 30 A | — | 96 ft | 154 ft | 244 ft | 389 ft | 618 ft | 983 ft |
| 40 A | — | — | 115 ft | 183 ft | 292 ft | 463 ft | 737 ft |
| 50 A | — | — | 92 ft | 146 ft | 233 ft | 371 ft | 590 ft |
| 60 A | — | — | — | 122 ft | 194 ft | 309 ft | 491 ft |
| 80 A | — | — | — | — | 146 ft | 231 ft | 368 ft |
| 100 A | — | — | — | — | — | 185 ft | 295 ft |
Common questions
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
How far can you run 12 gauge wire on a 20 amp circuit?
At a full 20 A, about 45 ft one way at 120 V before reaching 3%. At the more typical 16 A load it is about 56 ft.