Voltage Drop Calculator

HomeVoltage drop

Voltage drop formula

Three forms of the same calculation, when to use each, and a calculator that applies them so you can check your hand math.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Check your answer

Fill in the circuit, then press the button.

Resistance method

VD = 2 × R × L × I ÷ 1,000

VD = 1.732 × R × L × I ÷ 1,000

R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.

K-factor method

VD = 2 × K × L × I ÷ CM

K is the resistance of a circular-mil-foot of conductor: about 12.9 for copper and 21.2 for aluminum at 75 °C. CM is the conductor area in circular mils. It gives nearly the same answer as the Table 8 method because Table 8 is K ÷ CM × 1,000 with stranding taken into account.

SizeCircular milsK ÷ CM × 1,000 (Cu)Table 8 (Cu)
14 AWG4,1103.1393.14
12 AWG6,5301.9751.98
10 AWG10,3801.2431.24
8 AWG16,5100.7810.778
6 AWG26,2400.4920.491
4 AWG41,7400.3090.308
2 AWG66,3600.1940.194
1/0 AWG105,6000.1220.122
4/0 AWG211,6000.0610.0608

Percent drop and voltage at the load

% = VD ÷ V × 100

V at load = V − VD

Solving for wire size

CM = 2 × K × L × I ÷ VD allowed

Pick the next standard size at or above that circular mil area, then confirm it carries the current. The wire size calculator does both steps.

Common questions

Which formula does the NEC use?

The NEC does not prescribe one. Its Chapter 9 Table 8 gives DC resistance and Table 9 gives AC impedance; both are accepted. For circuits below 1/0, the two give almost the same result.

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
  • https://www.southwire.com/calculator-vdrop