Voltage Drop Calculator

HomeVoltage drop

Single-phase voltage drop calculator

For 120 V, 208 V and 240 V single-phase circuits in homes and small buildings. Current flows out on one conductor and back on the other, so the drop is figured on twice the one-way length.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Voltage drop

Fill in the circuit, then press the button.

Single-phase formula

VD = 2 × R × L × I ÷ 1,000

R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.

Worked example

A 40 A load on 8 AWG copper, 120 ft from the panel at 240 V. Table 8 gives 0.778 Ω per 1,000 ft. VD = 2 × 0.778 × 120 × 40 ÷ 1,000 = 7.47 V, or 3.11% of 240 V. That is just over 3%, so 6 AWG (0.491 Ω) would bring it to 4.71 V, 1.96%.

Smallest copper size for 3% at 240 V

Load50 ft100 ft150 ft200 ft300 ft
20 A12 AWG10 AWG8 AWG8 AWG6 AWG
30 A10 AWG8 AWG8 AWG6 AWG4 AWG
40 A8 AWG8 AWG6 AWG4 AWG3 AWG
50 A8 AWG6 AWG4 AWG4 AWG2 AWG
60 A6 AWG6 AWG4 AWG3 AWG2 AWG
80 A4 AWG4 AWG3 AWG2 AWG1/0 AWG
100 A3 AWG3 AWG2 AWG1 AWG2/0 AWG

Each cell is the smallest size that both carries the current at 75 °C and stays within 3%.

Smallest copper size for 3% at 120 V

Load25 ft50 ft75 ft100 ft150 ft
10 A14 AWG14 AWG12 AWG10 AWG8 AWG
15 A14 AWG12 AWG10 AWG8 AWG8 AWG
20 A12 AWG10 AWG8 AWG8 AWG6 AWG
30 A10 AWG8 AWG8 AWG6 AWG4 AWG

Common questions

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Is 3% voltage drop a code requirement?

Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.

Is 120/240 V split-phase calculated as single-phase?

Yes. A 240 V load between the two hots uses the single-phase formula. For a balanced 120/240 V feeder, figure the drop on one hot at its current; the neutral carries little or no current and adds nothing.