Single-phase voltage drop calculator
For 120 V, 208 V and 240 V single-phase circuits in homes and small buildings. Current flows out on one conductor and back on the other, so the drop is figured on twice the one-way length.
Voltage drop
Fill in the circuit, then press the button.
Single-phase formula
VD = 2 × R × L × I ÷ 1,000
R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.
Worked example
A 40 A load on 8 AWG copper, 120 ft from the panel at 240 V. Table 8 gives 0.778 Ω per 1,000 ft. VD = 2 × 0.778 × 120 × 40 ÷ 1,000 = 7.47 V, or 3.11% of 240 V. That is just over 3%, so 6 AWG (0.491 Ω) would bring it to 4.71 V, 1.96%.
Smallest copper size for 3% at 240 V
| Load | 50 ft | 100 ft | 150 ft | 200 ft | 300 ft |
|---|---|---|---|---|---|
| 20 A | 12 AWG | 10 AWG | 8 AWG | 8 AWG | 6 AWG |
| 30 A | 10 AWG | 8 AWG | 8 AWG | 6 AWG | 4 AWG |
| 40 A | 8 AWG | 8 AWG | 6 AWG | 4 AWG | 3 AWG |
| 50 A | 8 AWG | 6 AWG | 4 AWG | 4 AWG | 2 AWG |
| 60 A | 6 AWG | 6 AWG | 4 AWG | 3 AWG | 2 AWG |
| 80 A | 4 AWG | 4 AWG | 3 AWG | 2 AWG | 1/0 AWG |
| 100 A | 3 AWG | 3 AWG | 2 AWG | 1 AWG | 2/0 AWG |
Each cell is the smallest size that both carries the current at 75 °C and stays within 3%.
Smallest copper size for 3% at 120 V
| Load | 25 ft | 50 ft | 75 ft | 100 ft | 150 ft |
|---|---|---|---|---|---|
| 10 A | 14 AWG | 14 AWG | 12 AWG | 10 AWG | 8 AWG |
| 15 A | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 8 AWG |
| 20 A | 12 AWG | 10 AWG | 8 AWG | 8 AWG | 6 AWG |
| 30 A | 10 AWG | 8 AWG | 8 AWG | 6 AWG | 4 AWG |
Common questions
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Is 3% voltage drop a code requirement?
Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.
Is 120/240 V split-phase calculated as single-phase?
Yes. A 240 V load between the two hots uses the single-phase formula. For a balanced 120/240 V feeder, figure the drop on one hot at its current; the neutral carries little or no current and adds nothing.