Aluminum wire voltage drop calculator

Aluminum feeders and service cable are cheaper but drop more voltage per foot. Choose aluminum below, enter the run, and compare it with copper.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Voltage drop

Fill in the circuit, then press the button.

Aluminum vs copper resistance

SizeCopper Ω/kftAluminum Ω/kftAluminum drops
6 AWG0.4910.8081.65×
4 AWG0.3080.5081.65×
2 AWG0.1940.3191.64×
1/0 AWG0.1220.2011.65×
2/0 AWG0.09670.1591.64×
4/0 AWG0.06080.11.64×
250 kcmil0.05150.08471.64×
350 kcmil0.03670.06051.65×
500 kcmil0.02580.04241.64×

NEC Chapter 9, Table 8, stranded, 75 °C.

Equivalent sizes

To match copper's voltage drop, aluminum usually goes up two sizes. To match its ampacity, often one or two sizes.

CopperAluminum with equal or lower drop
10 AWG6 AWG
8 AWG4 AWG
6 AWG3 AWG
4 AWG1 AWG
2 AWG2/0 AWG
1 AWG3/0 AWG
1/0 AWG4/0 AWG
2/0 AWG250 kcmil
3/0 AWG300 kcmil
4/0 AWG350 kcmil
250 kcmil500 kcmil
350 kcmil600 kcmil

Common questions

Is aluminum wire safe for feeders?

Modern AA-8000 series aluminum conductors are widely used for services and feeders when terminated on lugs rated AL7CU or AL9CU with the right torque. Small aluminum branch circuits (15 and 20 A) need devices listed CO/ALR or special connectors.

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)