Aluminum wire voltage drop calculator
Aluminum feeders and service cable are cheaper but drop more voltage per foot. Choose aluminum below, enter the run, and compare it with copper.
Voltage drop
Fill in the circuit, then press the button.
Aluminum vs copper resistance
| Size | Copper Ω/kft | Aluminum Ω/kft | Aluminum drops |
|---|---|---|---|
| 6 AWG | 0.491 | 0.808 | 1.65× |
| 4 AWG | 0.308 | 0.508 | 1.65× |
| 2 AWG | 0.194 | 0.319 | 1.64× |
| 1/0 AWG | 0.122 | 0.201 | 1.65× |
| 2/0 AWG | 0.0967 | 0.159 | 1.64× |
| 4/0 AWG | 0.0608 | 0.1 | 1.64× |
| 250 kcmil | 0.0515 | 0.0847 | 1.64× |
| 350 kcmil | 0.0367 | 0.0605 | 1.65× |
| 500 kcmil | 0.0258 | 0.0424 | 1.64× |
NEC Chapter 9, Table 8, stranded, 75 °C.
Equivalent sizes
To match copper's voltage drop, aluminum usually goes up two sizes. To match its ampacity, often one or two sizes.
| Copper | Aluminum with equal or lower drop |
|---|---|
| 10 AWG | 6 AWG |
| 8 AWG | 4 AWG |
| 6 AWG | 3 AWG |
| 4 AWG | 1 AWG |
| 2 AWG | 2/0 AWG |
| 1 AWG | 3/0 AWG |
| 1/0 AWG | 4/0 AWG |
| 2/0 AWG | 250 kcmil |
| 3/0 AWG | 300 kcmil |
| 4/0 AWG | 350 kcmil |
| 250 kcmil | 500 kcmil |
| 350 kcmil | 600 kcmil |
Common questions
Is aluminum wire safe for feeders?
Modern AA-8000 series aluminum conductors are widely used for services and feeders when terminated on lugs rated AL7CU or AL9CU with the right torque. Small aluminum branch circuits (15 and 20 A) need devices listed CO/ALR or special connectors.
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.