NEC voltage drop rules
Most NEC voltage drop language is advice, not law. A handful of articles do set enforceable limits. Here is where each one sits.
Check a circuit
Fill in the circuit, then press the button.
Advisory notes
- 210.19, branch circuits. An informational note suggests sizing branch-circuit conductors so drop does not exceed 3% at the farthest outlet, with a 5% total for feeder plus branch.
- 215.2, feeders. A matching note suggests 3% on the feeder and 5% total.
Informational notes are explanatory and not enforceable (90.5(C)), but plan reviewers and engineers routinely apply them.
Enforceable limits
- 647.4(D): sensitive electronic equipment on separately derived 60/120 V systems: 1.5% on branch circuits, 2.5% combined.
- 695.7: fire pump controllers must not drop below 85% of rated voltage while the motor starts, and the motor terminals must stay within 5% of rated voltage running at 115% of full-load current.
- 690 and 705: no fixed limit for PV, but the conductors must be sized for 125% of maximum current, which often settles the size before voltage drop does.
Where the 3% becomes mandatory
Energy codes that adopt ASHRAE 90.1 limit feeders plus branch circuits to 5% combined. Federal, healthcare and many commercial specifications write 2% feeder and 3% branch into the contract. Equipment instructions, which the NEC requires you to follow under 110.3(B), sometimes set their own maximum, especially for well pumps, EV chargers and HVAC.
Common questions
Is 3% voltage drop a code requirement?
Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.
Did the 2023 NEC change voltage drop rules?
No new general limit was added. The suggestions remain in informational notes; the enforceable sections for sensitive electronics and fire pumps carried over.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)