Voltage Drop Calculator

HomeVoltage drop

DC voltage drop calculator

For battery, solar, automotive, marine and low-voltage lighting circuits. DC has no reactance, so the resistance formula is exact apart from temperature.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Voltage drop

Fill in the circuit, then press the button.

DC formula

VD = 2 × R × L × I ÷ 1,000

L is the one-way length. If the circuit returns through a metal frame instead of a wire, enter half the length, since only the positive conductor carries the current through copper.

Gauge for 3% drop at 12 V

Current5 ft10 ft15 ft20 ft30 ft
5 A16 AWG14 AWG12 AWG10 AWG8 AWG
10 A14 AWG10 AWG8 AWG8 AWG6 AWG
20 A10 AWG8 AWG6 AWG4 AWG3 AWG
30 A8 AWG6 AWG4 AWG3 AWG2 AWG
50 A6 AWG4 AWG2 AWG1 AWG2/0 AWG
100 A4 AWG1 AWG2/0 AWG3/0 AWG250 kcmil
150 A2 AWG2/0 AWG3/0 AWG250 kcmil350 kcmil

Gauge for 3% drop at 24 V

Current5 ft10 ft15 ft20 ft30 ft50 ft
5 A18 AWG16 AWG14 AWG14 AWG12 AWG10 AWG
10 A16 AWG14 AWG12 AWG10 AWG8 AWG6 AWG
20 A14 AWG10 AWG8 AWG8 AWG6 AWG4 AWG
30 A12 AWG8 AWG8 AWG6 AWG4 AWG2 AWG
50 A10 AWG6 AWG4 AWG4 AWG2 AWG1/0 AWG
100 A6 AWG4 AWG2 AWG1 AWG2/0 AWG4/0 AWG
150 A4 AWG2 AWG1 AWG2/0 AWG3/0 AWG300 kcmil

Common questions

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

What size wire for 12 V at 20 ft?

At 10 A and 3% drop, 20 ft one way needs 8 AWG copper. At 20 A it needs 4 AWG.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
  • ABYC E-11, AC and DC Electrical Systems on Boats (https://abycinc.org/)