Low voltage and electronics
Conductor materials
Copper and aluminum in standard building sizes use NEC Table 8. Silver, gold, tungsten, iron, platinum and steel, and any odd or fine gauge, are figured from resistivity and cross-section, then corrected for temperature.
| Material | Resistivity at 20 °C | Temperature coefficient | Drop compared with copper |
|---|---|---|---|
| Silver | 1.59 × 10⁻⁸ Ω·m | 0.0038 per °C | 0.92× |
| Copper | 1.72 × 10⁻⁸ Ω·m | 0.0039 per °C | 1.00× |
| Gold | 2.44 × 10⁻⁸ Ω·m | 0.0034 per °C | 1.42× |
| Aluminum | 2.65 × 10⁻⁸ Ω·m | 0.0040 per °C | 1.54× |
| Tungsten | 5.60 × 10⁻⁸ Ω·m | 0.0045 per °C | 3.26× |
| Iron | 9.71 × 10⁻⁸ Ω·m | 0.0050 per °C | 5.65× |
| Platinum | 10.60 × 10⁻⁸ Ω·m | 0.0039 per °C | 6.16× |
| Steel | 20.00 × 10⁻⁸ Ω·m | 0.0030 per °C | 11.63× |
Typical handbook values for the pure metals. Iron and steel vary widely by alloy.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
- ASTM B258, Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires