120 volt voltage drop calculator
120 V branch circuits feed lights, receptacles and small appliances. They are the most sensitive to distance because every volt lost is a bigger share of a small supply. Enter your wire size, load and distance.
Voltage drop
Fill in the circuit, then press the button.
Volts allowed at 120 V
| Target | 1% | 2% | 3% | 5% |
|---|---|---|---|---|
| Volts lost | 1.2 V | 2.4 V | 3.6 V | 6.0 V |
At 120 V, the NEC's 3% suggestion means losing no more than 3.6 V between the panel and the load, leaving 116.4 V at the equipment.
Maximum one-way distance at 3%, 120 V single-phase
| Load | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG |
|---|---|---|---|---|---|
| 15 A | 38 ft | 60 ft | 96 ft | 154 ft | 244 ft |
| 20 A | — | 45 ft | 72 ft | 115 ft | 183 ft |
| 30 A | — | — | 48 ft | 77 ft | 122 ft |
Copper, 75 °C ampacity. A dash means the wire is too small for that current. For aluminum, multiply each distance by about 0.61.
Drop on 12 AWG at 16 A
| One-way length | Drop | Drop % | At the load |
|---|---|---|---|
| 25 ft | 1.58 V | 1.32% | 118.4 V |
| 50 ft | 3.17 V | 2.64% | 116.8 V |
| 100 ft | 6.34 V | 5.28% | 113.7 V |
| 150 ft | 9.50 V | 7.92% | 110.5 V |
| 200 ft | 12.67 V | 10.56% | 107.3 V |
| 300 ft | 19.01 V | 15.84% | 101.0 V |
R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.
Common questions
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Is 3% voltage drop a code requirement?
Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.
How far can I run 12 AWG at 120 V?
At 15 A, 12 AWG copper reaches about 60 ft one way before the drop passes 3%. Double the current and the distance halves.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
- https://www.southwire.com/calculator-vdrop