Voltage Drop Calculator

HomeVoltage drop

120 volt voltage drop calculator

120 V branch circuits feed lights, receptacles and small appliances. They are the most sensitive to distance because every volt lost is a bigger share of a small supply. Enter your wire size, load and distance.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Voltage drop

Fill in the circuit, then press the button.

Volts allowed at 120 V

Target1%2%3%5%
Volts lost1.2 V2.4 V3.6 V6.0 V

At 120 V, the NEC's 3% suggestion means losing no more than 3.6 V between the panel and the load, leaving 116.4 V at the equipment.

Maximum one-way distance at 3%, 120 V single-phase

Load14 AWG12 AWG10 AWG8 AWG6 AWG
15 A38 ft60 ft96 ft154 ft244 ft
20 A—45 ft72 ft115 ft183 ft
30 A——48 ft77 ft122 ft

Copper, 75 °C ampacity. A dash means the wire is too small for that current. For aluminum, multiply each distance by about 0.61.

Drop on 12 AWG at 16 A

One-way lengthDropDrop %At the load
25 ft1.58 V1.32%118.4 V
50 ft3.17 V2.64%116.8 V
100 ft6.34 V5.28%113.7 V
150 ft9.50 V7.92%110.5 V
200 ft12.67 V10.56%107.3 V
300 ft19.01 V15.84%101.0 V

R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.

Common questions

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Is 3% voltage drop a code requirement?

Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.

How far can I run 12 AWG at 120 V?

At 15 A, 12 AWG copper reaches about 60 ft one way before the drop passes 3%. Double the current and the distance halves.