Voltage Drop Calculator

HomeWire size

Wire size by voltage drop

The right wire is the larger of two answers: the size that carries the current, and the size that keeps voltage drop in check. This calculator finds both and gives you the bigger one.

V
A
One way, from the source to the load.
%

Wire size

Fill in the circuit, then press the button.

Smallest copper size, 240 V single-phase, 3%

Load50 ft100 ft150 ft200 ft250 ft300 ft400 ft
15 A14 AWG12 AWG10 AWG8 AWG8 AWG8 AWG6 AWG
20 A12 AWG10 AWG8 AWG8 AWG6 AWG6 AWG4 AWG
30 A10 AWG8 AWG8 AWG6 AWG4 AWG4 AWG3 AWG
40 A8 AWG8 AWG6 AWG4 AWG4 AWG3 AWG2 AWG
50 A8 AWG6 AWG4 AWG4 AWG3 AWG2 AWG1 AWG
60 A6 AWG6 AWG4 AWG3 AWG2 AWG2 AWG1/0 AWG
80 A4 AWG4 AWG3 AWG2 AWG1 AWG1/0 AWG2/0 AWG
100 A3 AWG3 AWG2 AWG1 AWG1/0 AWG2/0 AWG3/0 AWG
125 A1 AWG1 AWG1 AWG1/0 AWG2/0 AWG3/0 AWG4/0 AWG
150 A1/0 AWG1/0 AWG1/0 AWG2/0 AWG3/0 AWG3/0 AWG250 kcmil
200 A3/0 AWG3/0 AWG3/0 AWG3/0 AWG4/0 AWG250 kcmil300 kcmil

Smallest copper size, 120 V, 3%

Load25 ft50 ft75 ft100 ft150 ft200 ft
5 A14 AWG14 AWG14 AWG14 AWG12 AWG10 AWG
10 A14 AWG14 AWG12 AWG10 AWG8 AWG8 AWG
15 A14 AWG12 AWG10 AWG8 AWG8 AWG6 AWG
20 A12 AWG10 AWG8 AWG8 AWG6 AWG4 AWG
30 A10 AWG8 AWG8 AWG6 AWG4 AWG3 AWG

Smallest aluminum size, 240 V, 3%

Load100 ft150 ft200 ft300 ft400 ft
60 A4 AWG2 AWG1 AWG2/0 AWG3/0 AWG
100 A1 AWG1/0 AWG2/0 AWG4/0 AWG250 kcmil
125 A2/0 AWG2/0 AWG3/0 AWG250 kcmil300 kcmil
150 A3/0 AWG3/0 AWG4/0 AWG300 kcmil400 kcmil
200 A250 kcmil250 kcmil250 kcmil400 kcmil500 kcmil

When voltage drop forces a larger wire, NEC 250.122(B) also requires the equipment ground to grow by the same ratio of circular mil area.

Common questions

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Is 3% voltage drop a code requirement?

Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
  • https://www.southwire.com/calculator-vdrop