Wire size by voltage drop
The right wire is the larger of two answers: the size that carries the current, and the size that keeps voltage drop in check. This calculator finds both and gives you the bigger one.
Wire size
Fill in the circuit, then press the button.
Smallest copper size, 240 V single-phase, 3%
| Load | 50 ft | 100 ft | 150 ft | 200 ft | 250 ft | 300 ft | 400 ft |
|---|---|---|---|---|---|---|---|
| 15 A | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 8 AWG | 8 AWG | 6 AWG |
| 20 A | 12 AWG | 10 AWG | 8 AWG | 8 AWG | 6 AWG | 6 AWG | 4 AWG |
| 30 A | 10 AWG | 8 AWG | 8 AWG | 6 AWG | 4 AWG | 4 AWG | 3 AWG |
| 40 A | 8 AWG | 8 AWG | 6 AWG | 4 AWG | 4 AWG | 3 AWG | 2 AWG |
| 50 A | 8 AWG | 6 AWG | 4 AWG | 4 AWG | 3 AWG | 2 AWG | 1 AWG |
| 60 A | 6 AWG | 6 AWG | 4 AWG | 3 AWG | 2 AWG | 2 AWG | 1/0 AWG |
| 80 A | 4 AWG | 4 AWG | 3 AWG | 2 AWG | 1 AWG | 1/0 AWG | 2/0 AWG |
| 100 A | 3 AWG | 3 AWG | 2 AWG | 1 AWG | 1/0 AWG | 2/0 AWG | 3/0 AWG |
| 125 A | 1 AWG | 1 AWG | 1 AWG | 1/0 AWG | 2/0 AWG | 3/0 AWG | 4/0 AWG |
| 150 A | 1/0 AWG | 1/0 AWG | 1/0 AWG | 2/0 AWG | 3/0 AWG | 3/0 AWG | 250 kcmil |
| 200 A | 3/0 AWG | 3/0 AWG | 3/0 AWG | 3/0 AWG | 4/0 AWG | 250 kcmil | 300 kcmil |
Smallest copper size, 120 V, 3%
| Load | 25 ft | 50 ft | 75 ft | 100 ft | 150 ft | 200 ft |
|---|---|---|---|---|---|---|
| 5 A | 14 AWG | 14 AWG | 14 AWG | 14 AWG | 12 AWG | 10 AWG |
| 10 A | 14 AWG | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 8 AWG |
| 15 A | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 8 AWG | 6 AWG |
| 20 A | 12 AWG | 10 AWG | 8 AWG | 8 AWG | 6 AWG | 4 AWG |
| 30 A | 10 AWG | 8 AWG | 8 AWG | 6 AWG | 4 AWG | 3 AWG |
Smallest aluminum size, 240 V, 3%
| Load | 100 ft | 150 ft | 200 ft | 300 ft | 400 ft |
|---|---|---|---|---|---|
| 60 A | 4 AWG | 2 AWG | 1 AWG | 2/0 AWG | 3/0 AWG |
| 100 A | 1 AWG | 1/0 AWG | 2/0 AWG | 4/0 AWG | 250 kcmil |
| 125 A | 2/0 AWG | 2/0 AWG | 3/0 AWG | 250 kcmil | 300 kcmil |
| 150 A | 3/0 AWG | 3/0 AWG | 4/0 AWG | 300 kcmil | 400 kcmil |
| 200 A | 250 kcmil | 250 kcmil | 250 kcmil | 400 kcmil | 500 kcmil |
When voltage drop forces a larger wire, NEC 250.122(B) also requires the equipment ground to grow by the same ratio of circular mil area.
Common questions
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Is 3% voltage drop a code requirement?
Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
- https://www.southwire.com/calculator-vdrop