Voltage Drop Calculator

HomeWire size

Wire size for 110 amps

A 110 amp circuit needs at least 2 AWG copper or 1/0 AWG aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.

V
A
One way, from the source to the load.
%

Wire size

Fill in the circuit, then press the button.

Minimum wire for 110 amps

Conductor60 °C75 °C90 °C
Copper1 AWG2 AWG3 AWG
Aluminum2/0 AWG1/0 AWG1 AWG

NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).

Most 110 A circuits land on 2 AWG copper or 1/0 AWG aluminum, using the 75 °C column. If the cable is NM-B (Romex) or any terminal is rated only 60 °C, use 1 AWG copper. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.

A 110 A service or main feeder for a single-family home may use the smaller sizes in Table 310.12: 3 AWG copper or 1 AWG aluminum.

How far can a 110 amp circuit run?

Maximum one-way distance at 3% drop with the circuit loaded to 88 A (80% of the breaker). Past these lengths, use the next column.

Voltage2 AWG1 AWG1/0 AWG2/0 AWG3/0 AWG
240 V210 ft265 ft335 ft423 ft534 ft
208 V 3φ211 ft265 ft335 ft423 ft534 ft
480 V 3φ486 ft613 ft774 ft976 ft1,233 ft

Copper. Three-phase rows use 1.732 in place of 2.

Other parts of a 110 A circuit

  • Equipment ground: 6 AWG copper or 4 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
  • Typical uses: subpanels and older services.
  • Continuous loads: a 110 A breaker can carry 88 A continuously (210.19, 215.2).

Common questions

Can I use 2 AWG for 110 amps?

Yes, 2 AWG copper is rated 115 A at 75 °C, enough for a 110 A breaker as long as every termination is rated 75 °C and the run is short enough for voltage drop, about 210 ft at 240 V.

What size aluminum wire for 110 amps?

1/0 AWG aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)