Wire size for 125 amps
A 125 amp circuit needs at least 1 AWG copper or 2/0 AWG aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.
Wire size
Fill in the circuit, then press the button.
Minimum wire for 125 amps
| Conductor | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| Copper | 1/0 AWG | 1 AWG | 2 AWG |
| Aluminum | 3/0 AWG | 2/0 AWG | 1/0 AWG |
NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).
Most 125 A circuits land on 1 AWG copper or 2/0 AWG aluminum, using the 75 °C column. If the cable is NM-B (Romex) or any terminal is rated only 60 °C, use 1/0 AWG copper. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.
A 125 A service or main feeder for a single-family home may use the smaller sizes in Table 310.12: 2 AWG copper or 1/0 AWG aluminum. See the 125 amp service page.
How far can a 125 amp circuit run?
Maximum one-way distance at 3% drop with the circuit loaded to 100 A (80% of the breaker). Past these lengths, use the next column.
| Voltage | 1 AWG | 1/0 AWG | 2/0 AWG | 3/0 AWG | 4/0 AWG |
|---|---|---|---|---|---|
| 240 V | 233 ft | 295 ft | 372 ft | 469 ft | 592 ft |
| 208 V 3φ | 233 ft | 295 ft | 372 ft | 470 ft | 592 ft |
| 480 V 3φ | 539 ft | 681 ft | 859 ft | 1,085 ft | 1,367 ft |
Copper. Three-phase rows use 1.732 in place of 2.
Other parts of a 125 A circuit
- Equipment ground: 6 AWG copper or 4 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
- Typical uses: subpanels and small homes.
- Continuous loads: a 125 A breaker can carry 100 A continuously (210.19, 215.2).
Common questions
Can I use 1 AWG for 125 amps?
Yes, 1 AWG copper is rated 130 A at 75 °C, enough for a 125 A breaker as long as every termination is rated 75 °C and the run is short enough for voltage drop, about 233 ft at 240 V.
What size aluminum wire for 125 amps?
2/0 AWG aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.