Wire size for 200 amps
A 200 amp circuit needs at least 3/0 AWG copper or 250 kcmil aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.
Wire size
Fill in the circuit, then press the button.
Minimum wire for 200 amps
| Conductor | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| Copper | 250 kcmil | 3/0 AWG | 3/0 AWG |
| Aluminum | 350 kcmil | 250 kcmil | 4/0 AWG |
NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).
Most 200 A circuits land on 3/0 AWG copper or 250 kcmil aluminum, using the 75 °C column. If the cable is NM-B (Romex) or any terminal is rated only 60 °C, use 250 kcmil copper. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.
A 200 A service or main feeder for a single-family home may use the smaller sizes in Table 310.12: 2/0 AWG copper or 4/0 AWG aluminum. See the 200 amp service page.
How far can a 200 amp circuit run?
Maximum one-way distance at 3% drop with the circuit loaded to 160 A (80% of the breaker). Past these lengths, use the next column.
| Voltage | 3/0 AWG | 4/0 AWG | 250 kcmil | 300 kcmil | 350 kcmil |
|---|---|---|---|---|---|
| 240 V | 293 ft | 370 ft | 436 ft | 524 ft | 613 ft |
| 208 V 3φ | 293 ft | 370 ft | 437 ft | 524 ft | 613 ft |
| 480 V 3φ | 678 ft | 854 ft | 1,008 ft | 1,211 ft | 1,415 ft |
Copper. Three-phase rows use 1.732 in place of 2.
Other parts of a 200 A circuit
- Equipment ground: 6 AWG copper or 4 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
- Typical uses: the most common house service, large subpanels.
- Continuous loads: a 200 A breaker can carry 160 A continuously (210.19, 215.2).
Common questions
Can I use 3/0 AWG for 200 amps?
Yes, 3/0 AWG copper is rated 200 A at 75 °C, enough for a 200 A breaker as long as every termination is rated 75 °C and the run is short enough for voltage drop, about 293 ft at 240 V.
What size aluminum wire for 200 amps?
250 kcmil aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)