200 amp service wire size
A 200 A single-family service may use 2/0 AWG copper or 4/0 AWG aluminum under NEC 310.12. Long underground laterals and feeders that serve only part of the building need more.
Service conductors
Fill in the circuit, then press the button.
200 A conductor sizes
| Use | Copper | Aluminum | Basis |
|---|---|---|---|
| Whole-dwelling service or main feeder | 2/0 AWG | 4/0 AWG | Table 310.12 (83% of rating) |
| Feeder to part of the building | 3/0 AWG | 250 kcmil | Table 310.16, 75 °C |
| Grounding electrode conductor | 4 AWG | 2 AWG | Table 250.66, based on the aluminum size |
Table 310.12 lets a one-family dwelling service be sized at 83% of its rating because the whole house never draws its full rating for long. It applies only where the conductors carry the entire dwelling load, and only for 120/240 V single-phase services. Correction factors for heat, such as conductors in a hot attic or on a sunny roof, still apply.
Voltage drop on a 200 A service
At 83% of rating (166 A), single-phase 240 V:
| One-way length | 4/0 AWG Al | 2/0 AWG Cu |
|---|---|---|
| 50 ft | 1.7 V (0.7%) | 1.6 V (0.7%) |
| 100 ft | 3.3 V (1.4%) | 3.2 V (1.3%) |
| 150 ft | 5.0 V (2.1%) | 4.8 V (2.0%) |
| 200 ft | 6.6 V (2.8%) | 6.4 V (2.7%) |
| 300 ft | 10.0 V (4.2%) | 9.6 V (4.0%) |
Most utilities own the drop or lateral to the meter; this applies to conductors you install. Meter-to-house runs over about 150 ft often go one or two sizes larger.
Cable choices
- SER (4 conductors) or SEU (3 conductors) for overhead service entrance runs.
- URD / USE-2 aluminum triplex or quadruplex for direct-burial laterals, 24 in deep under Table 300.5.
- XHHW-2 or THWN-2 in conduit.
The neutral may be smaller than the hots when the calculated neutral load allows (220.61), but not smaller than the grounding electrode conductor (250.24(C)).
Common questions
Can I use 4/0 AWG aluminum for a 200 amp service?
Yes, for a single-family dwelling service under 310.12. For a 200 A feeder that is not the main service, use 250 kcmil aluminum.
Does 310.12 apply to a subpanel?
Only if that panel is fed by conductors carrying the entire dwelling load, such as a main disconnect outside feeding the interior panel. A garage or shop subpanel uses Table 310.16.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)