300 amp service wire size

A 300 A single-family service may use 250 kcmil copper or 350 kcmil aluminum under NEC 310.12. Long underground laterals and feeders that serve only part of the building need more.

One way. Enter 0 to skip voltage drop.
V
%

Service conductors

Fill in the circuit, then press the button.

300 A conductor sizes

UseCopperAluminumBasis
Whole-dwelling service or main feeder250 kcmil350 kcmilTable 310.12 (83% of rating)
Feeder to part of the building350 kcmil500 kcmilTable 310.16, 75 °C
Grounding electrode conductor2 AWG1/0 AWGTable 250.66, based on the aluminum size

Table 310.12 lets a one-family dwelling service be sized at 83% of its rating because the whole house never draws its full rating for long. It applies only where the conductors carry the entire dwelling load, and only for 120/240 V single-phase services. Correction factors for heat, such as conductors in a hot attic or on a sunny roof, still apply.

Voltage drop on a 300 A service

At 83% of rating (249 A), single-phase 240 V:

One-way length350 kcmil Al250 kcmil Cu
50 ft1.5 V (0.6%)1.3 V (0.5%)
100 ft3.0 V (1.3%)2.6 V (1.1%)
150 ft4.5 V (1.9%)3.8 V (1.6%)
200 ft6.0 V (2.5%)5.1 V (2.1%)
300 ft9.0 V (3.8%)7.7 V (3.2%)

Most utilities own the drop or lateral to the meter; this applies to conductors you install. Meter-to-house runs over about 150 ft often go one or two sizes larger.

Cable choices

  • SER (4 conductors) or SEU (3 conductors) for overhead service entrance runs.
  • URD / USE-2 aluminum triplex or quadruplex for direct-burial laterals, 24 in deep under Table 300.5.
  • XHHW-2 or THWN-2 in conduit.

The neutral may be smaller than the hots when the calculated neutral load allows (220.61), but not smaller than the grounding electrode conductor (250.24(C)).

Common questions

Can I use 350 kcmil aluminum for a 300 amp service?

Yes, for a single-family dwelling service under 310.12. For a 300 A feeder that is not the main service, use 500 kcmil aluminum.

Does 310.12 apply to a subpanel?

Only if that panel is fed by conductors carrying the entire dwelling load, such as a main disconnect outside feeding the interior panel. A garage or shop subpanel uses Table 310.16.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)