150 amp subpanel wire size

A 150 A subpanel feeder needs 1/0 AWG copper or 3/0 AWG aluminum at 75 °C, plus a ground. Detached garages and shops are often far enough away that voltage drop sets the size.

One way. Enter 0 to skip voltage drop.
V
%

Feeder size

Fill in the circuit, then press the button.

150 A feeder

PartCopperAluminum
Hots and neutral1/0 AWG3/0 AWG
Equipment ground6 AWG4 AWG

Table 310.16, 75 °C terminals, and Table 250.122.

A subpanel needs four wires: two hots, a neutral and a ground. In the subpanel the neutral bar is isolated from the enclosure and the ground bar is bonded to it. A detached building also needs its own grounding electrode (250.32).

Maximum distance at 3%, 120 A load, 240 V

CopperAmpacityMax distance
1/0 AWG150 A245 ft
2/0 AWG175 A310 ft
3/0 AWG200 A391 ft
4/0 AWG230 A493 ft
AluminumAmpacityMax distance
3/0 AWG155 A238 ft
4/0 AWG180 A300 ft
250 kcmil205 A354 ft
300 kcmil230 A424 ft

Based on 80% of the breaker rating, a realistic heavy load. If the panel will see lighter use, 5% total is still within NEC guidance.

Common questions

What size wire for a 150 amp subpanel 100 feet away?

At 100 ft, 1 AWG copper or 1/0 AWG aluminum keeps the drop under 3% at 120 A.

What size wire for a 150 amp subpanel 200 feet away?

At 200 ft, 1/0 AWG copper or 3/0 AWG aluminum keeps the drop under 3% at 120 A.

Can I feed a subpanel with 3 wires?

Not for new work. Since the 2008 NEC, feeders to detached buildings need a separate equipment ground (250.32(B)).