Voltage Drop Calculator

HomeCircuits

100 amp subpanel wire size

A 100 A subpanel feeder needs 3 AWG copper or 1 AWG aluminum at 75 °C, plus a ground. Detached garages and shops are often far enough away that voltage drop sets the size.

One way. Enter 0 to skip voltage drop.
V
%

Feeder size

Fill in the circuit, then press the button.

100 A feeder

PartCopperAluminum
Hots and neutral3 AWG1 AWG
Equipment ground8 AWG6 AWG

Table 310.16, 75 °C terminals, and Table 250.122.

A subpanel needs four wires: two hots, a neutral and a ground. In the subpanel the neutral bar is isolated from the enclosure and the ground bar is bonded to it. A detached building also needs its own grounding electrode (250.32).

Maximum distance at 3%, 80 A load, 240 V

CopperAmpacityMax distance
3 AWG100 A183 ft
2 AWG115 A231 ft
1 AWG130 A292 ft
1/0 AWG150 A368 ft
AluminumAmpacityMax distance
1 AWG100 A177 ft
1/0 AWG120 A223 ft
2/0 AWG135 A283 ft
3/0 AWG155 A357 ft

Based on 80% of the breaker rating, a realistic heavy load. If the panel will see lighter use, 5% total is still within NEC guidance.

Common questions

What size wire for a 100 amp subpanel 100 feet away?

At 100 ft, 4 AWG copper or 2 AWG aluminum keeps the drop under 3% at 80 A.

What size wire for a 100 amp subpanel 200 feet away?

At 200 ft, 2 AWG copper or 1/0 AWG aluminum keeps the drop under 3% at 80 A.

Can I feed a subpanel with 3 wires?

Not for new work. Since the 2008 NEC, feeders to detached buildings need a separate equipment ground (250.32(B)).

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)