60 amp subpanel wire size
A 60 A subpanel feeder needs 6 AWG copper or 4 AWG aluminum at 75 °C, plus a ground. Detached garages and shops are often far enough away that voltage drop sets the size.
Feeder size
Fill in the circuit, then press the button.
60 A feeder
| Part | Copper | Aluminum |
|---|---|---|
| Hots and neutral | 6 AWG | 4 AWG |
| Equipment ground | 10 AWG | 8 AWG |
Table 310.16, 75 °C terminals, and Table 250.122.
For 60 A the 60 °C column may apply: NM-B cable or 60 °C breaker terminals need 4 AWG copper (70 A); 6 AWG NM-B is rated 55 A.
A subpanel needs four wires: two hots, a neutral and a ground. In the subpanel the neutral bar is isolated from the enclosure and the ground bar is bonded to it. A detached building also needs its own grounding electrode (250.32).
Maximum distance at 3%, 48 A load, 240 V
| Copper | Ampacity | Max distance |
|---|---|---|
| 6 AWG | 65 A | 152 ft |
| 4 AWG | 85 A | 243 ft |
| 3 AWG | 100 A | 306 ft |
| 2 AWG | 115 A | 386 ft |
| Aluminum | Ampacity | Max distance |
|---|---|---|
| 4 AWG | 65 A | 147 ft |
| 3 AWG | 75 A | 186 ft |
| 2 AWG | 90 A | 235 ft |
| 1 AWG | 100 A | 296 ft |
Based on 80% of the breaker rating, a realistic heavy load. If the panel will see lighter use, 5% total is still within NEC guidance.
Common questions
What size wire for a 60 amp subpanel 100 feet away?
At 100 ft, 6 AWG copper or 4 AWG aluminum keeps the drop under 3% at 48 A.
What size wire for a 60 amp subpanel 200 feet away?
At 200 ft, 4 AWG copper or 2 AWG aluminum keeps the drop under 3% at 48 A.
Can I feed a subpanel with 3 wires?
Not for new work. Since the 2008 NEC, feeders to detached buildings need a separate equipment ground (250.32(B)).