Voltage Drop Calculator

HomeCircuits

60 amp subpanel wire size

A 60 A subpanel feeder needs 6 AWG copper or 4 AWG aluminum at 75 °C, plus a ground. Detached garages and shops are often far enough away that voltage drop sets the size.

V
A
One way, from the source to the load.
%

Feeder size

Fill in the circuit, then press the button.

60 A feeder

PartCopperAluminum
Hots and neutral6 AWG4 AWG
Equipment ground10 AWG8 AWG

Table 310.16, 75 °C terminals, and Table 250.122.

For 60 A the 60 °C column may apply: NM-B cable or 60 °C breaker terminals need 4 AWG copper (70 A); 6 AWG NM-B is rated 55 A.

A subpanel needs four wires: two hots, a neutral and a ground. In the subpanel the neutral bar is isolated from the enclosure and the ground bar is bonded to it. A detached building also needs its own grounding electrode (250.32).

Maximum distance at 3%, 48 A load, 240 V

CopperAmpacityMax distance
6 AWG65 A152 ft
4 AWG85 A243 ft
3 AWG100 A306 ft
2 AWG115 A386 ft
AluminumAmpacityMax distance
4 AWG65 A147 ft
3 AWG75 A186 ft
2 AWG90 A235 ft
1 AWG100 A296 ft

Based on 80% of the breaker rating, a realistic heavy load. If the panel will see lighter use, 5% total is still within NEC guidance.

Common questions

What size wire for a 60 amp subpanel 100 feet away?

At 100 ft, 6 AWG copper or 4 AWG aluminum keeps the drop under 3% at 48 A.

What size wire for a 60 amp subpanel 200 feet away?

At 200 ft, 4 AWG copper or 2 AWG aluminum keeps the drop under 3% at 48 A.

Can I feed a subpanel with 3 wires?

Not for new work. Since the 2008 NEC, feeders to detached buildings need a separate equipment ground (250.32(B)).

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)