32 amp EV charger wire size

A charger set to 32 A is a continuous load, so the circuit is sized at 125%: a 40 A breaker. 32 A is the most common Level 2 home charger setting, about 7.7 kW.

V
One way from the panel. Enter 0 to skip voltage drop.
%

EV charger circuit

Fill in the circuit, then press the button.

32 A charger circuit

PartSize
Breaker40 A, 2-pole
THHN/THWN-2 copper in conduit (75 °C)8 AWG
NM-B cable (60 °C)8 AWG/2 with ground
Aluminum (75 °C)8 AWG
Equipment ground10 AWG copper

NEC 625.40 and 625.41: the branch circuit and its overcurrent device are sized for 125% of the charger's maximum load.

Hardwired chargers adjust their maximum current with a switch or app; set it to match the circuit. A plug-in charger on a NEMA 14-50 receptacle is limited to 40 A, and receptacle installations need GFCI protection (210.8(F) and 625.54).

How far can the 40 A circuit run?

WireAmpacity3% at 240 V
8 AWG50 A144 ft
6 AWG65 A229 ft
4 AWG85 A365 ft
3 AWG100 A459 ft

Measured at the charger's full current. Panels on the far side of the house often need one size larger.

Common questions

What breaker for a 32 amp EV charger?

40 A. The charger's 32 A is a continuous load, and 125% of 32 A is 40 A.

Do I need a load calculation?

Yes. Adding a 7 to 19 kW load can push a service past its rating. NEC 220.87 allows using a year of utility demand data, and 625.42 allows an energy management system to cap the charger.