48 amp EV charger wire size
A charger set to 48 A is a continuous load, so the circuit is sized at 125%: a 60 A breaker. 48 A is about 11.5 kW, the highest setting for most plug-in and hardwired home chargers.
EV charger circuit
Fill in the circuit, then press the button.
48 A charger circuit
| Part | Size |
|---|---|
| Breaker | 60 A, 2-pole |
| THHN/THWN-2 copper in conduit (75 °C) | 6 AWG |
| NM-B cable (60 °C) | 4 AWG/2 with ground |
| Aluminum (75 °C) | 4 AWG |
| Equipment ground | 10 AWG copper |
NEC 625.40 and 625.41: the branch circuit and its overcurrent device are sized for 125% of the charger's maximum load.
Hardwired chargers adjust their maximum current with a switch or app; set it to match the circuit. A plug-in charger on a NEMA 14-50 receptacle is limited to 40 A, and receptacle installations need GFCI protection (210.8(F) and 625.54).
How far can the 60 A circuit run?
| Wire | Ampacity | 3% at 240 V |
|---|---|---|
| 6 AWG | 65 A | 152 ft |
| 4 AWG | 85 A | 243 ft |
| 3 AWG | 100 A | 306 ft |
| 2 AWG | 115 A | 386 ft |
Measured at the charger's full current. Panels on the far side of the house often need one size larger.
Common questions
What breaker for a 48 amp EV charger?
60 A. The charger's 48 A is a continuous load, and 125% of 48 A is 60 A.
Do I need a load calculation?
Yes. Adding a 7 to 19 kW load can push a service past its rating. NEC 220.87 allows using a year of utility demand data, and 625.42 allows an energy management system to cap the charger.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
- https://afdc.energy.gov/fuels/electricity-infrastructure-development