Wire burial depth calculator
Choose where the run goes and how it is installed. The answer is the minimum cover, measured from finished grade to the top of the cable or conduit.
Minimum cover
Fill in the circuit, then press the button.
Table 300.5 at a glance
| Location | UF | RMC | PVC | GFCI 20 A | ≤30 V |
|---|---|---|---|---|---|
| General: lawns, open ground, anywhere not listed below | 24 in | 6 in | 18 in | 12 in | 6 in |
| In a trench under at least 2 in of concrete | 18 in | 6 in | 12 in | 6 in | 6 in |
| Under a 4 in exterior slab with no vehicle traffic, extending 6 in past the run | 18 in | 4 in | 4 in | 6 in | 6 in |
| Under a one- or two-family dwelling driveway or parking area | 18 in | 18 in | 18 in | 12 in | 18 in |
| Under streets, roads, alleys, public driveways and parking lots | 24 in | 24 in | 24 in | 24 in | 24 in |
| Under a building (raceway or cable listed for it) | 0 in | 0 in | 0 in | 0 in | 0 in |
Other underground rules
- Use wire rated for wet locations (THWN-2, XHHW-2, UF, USE-2) in underground conduit; it is considered wet inside.
- Seal or plug conduit ends where they enter a building (300.5(G)).
- Place a warning ribbon at least 12 in above service conductors that are not encased in concrete and are 18 in or more deep (300.5(D)(3)).
- Backfill with no large rocks against the cable (300.5(F)).
Common questions
How deep do you bury electrical wire?
24 in for direct-burial UF cable, 18 in for PVC conduit, 6 in for rigid metal conduit, and 12 in for a GFCI-protected residential 120 V circuit of 20 A or less, in an ordinary yard.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)