Voltage Drop Calculator

HomeCircuits

Wire burial depth calculator

Choose where the run goes and how it is installed. The answer is the minimum cover, measured from finished grade to the top of the cable or conduit.

Minimum cover

Fill in the circuit, then press the button.

Table 300.5 at a glance

LocationUFRMCPVCGFCI 20 A≤30 V
General: lawns, open ground, anywhere not listed below24 in6 in18 in12 in6 in
In a trench under at least 2 in of concrete18 in6 in12 in6 in6 in
Under a 4 in exterior slab with no vehicle traffic, extending 6 in past the run18 in4 in4 in6 in6 in
Under a one- or two-family dwelling driveway or parking area18 in18 in18 in12 in18 in
Under streets, roads, alleys, public driveways and parking lots24 in24 in24 in24 in24 in
Under a building (raceway or cable listed for it)0 in0 in0 in0 in0 in

Other underground rules

  • Use wire rated for wet locations (THWN-2, XHHW-2, UF, USE-2) in underground conduit; it is considered wet inside.
  • Seal or plug conduit ends where they enter a building (300.5(G)).
  • Place a warning ribbon at least 12 in above service conductors that are not encased in concrete and are 18 in or more deep (300.5(D)(3)).
  • Backfill with no large rocks against the cable (300.5(F)).

Common questions

How deep do you bury electrical wire?

24 in for direct-burial UF cable, 18 in for PVC conduit, 6 in for rigid metal conduit, and 12 in for a GFCI-protected residential 120 V circuit of 20 A or less, in an ordinary yard.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)