Grounding electrode conductor size
The GEC runs from the service to the ground rods, water pipe or footing electrode. It is sized from the largest service conductor. Choose the service rating and material below.
Service and GEC
Fill in the circuit, then press the button.
Table 250.66
| Largest service conductor, copper | Aluminum | GEC copper | GEC aluminum |
|---|---|---|---|
| 2 AWG or smaller | 1/0 or smaller | 8 AWG | 6 AWG |
| 1 or 1/0 | 2/0 or 3/0 | 6 AWG | 4 AWG |
| 2/0 or 3/0 | 4/0 or 250 | 4 AWG | 2 AWG |
| over 3/0 to 350 | over 250 to 500 | 2 AWG | 1/0 AWG |
| over 350 to 600 | over 500 to 900 | 1/0 AWG | 3/0 AWG |
| over 600 to 1100 | over 900 to 1750 | 2/0 AWG | 4/0 AWG |
| over 1100 | over 1750 | 3/0 AWG | 250 kcmil |
Smaller limits by electrode
- Ground rods: the GEC never has to be larger than 6 AWG copper or 4 AWG aluminum (250.66(A)).
- Concrete-encased electrode (Ufer): never larger than 4 AWG copper (250.66(B)).
- Ground ring: no larger than the ring conductor (250.66(C)).
A metal water pipe electrode uses the full table size.
Common questions
What size ground wire for a 200 amp service?
With 2/0 copper or 4/0 aluminum service conductors, the GEC is 4 AWG copper or 2 AWG aluminum. The run to ground rods alone may be 6 AWG copper.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)