Voltage Drop Calculator

HomeCircuits

Grounding electrode conductor size

The GEC runs from the service to the ground rods, water pipe or footing electrode. It is sized from the largest service conductor. Choose the service rating and material below.

One way. Enter 0 to skip voltage drop.
V
%

Service and GEC

Fill in the circuit, then press the button.

Table 250.66

Largest service conductor, copperAluminumGEC copperGEC aluminum
2 AWG or smaller1/0 or smaller8 AWG6 AWG
1 or 1/02/0 or 3/06 AWG4 AWG
2/0 or 3/04/0 or 2504 AWG2 AWG
over 3/0 to 350over 250 to 5002 AWG1/0 AWG
over 350 to 600over 500 to 9001/0 AWG3/0 AWG
over 600 to 1100over 900 to 17502/0 AWG4/0 AWG
over 1100over 17503/0 AWG250 kcmil

Smaller limits by electrode

  • Ground rods: the GEC never has to be larger than 6 AWG copper or 4 AWG aluminum (250.66(A)).
  • Concrete-encased electrode (Ufer): never larger than 4 AWG copper (250.66(B)).
  • Ground ring: no larger than the ring conductor (250.66(C)).

A metal water pipe electrode uses the full table size.

Common questions

What size ground wire for a 200 amp service?

With 2/0 copper or 4/0 aluminum service conductors, the GEC is 4 AWG copper or 2 AWG aluminum. The run to ground rods alone may be 6 AWG copper.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)