Voltage Drop Calculator

HomeCircuits

Dryer wire size

Most electric dryers need a 30 A, 240 V circuit on 10 AWG copper. New installations use four wires: two hots, neutral and ground, ending in a NEMA 14-30 receptacle.

V
One way from the panel. Enter 0 to skip voltage drop.
%

Dryer circuit

Fill in the circuit, then press the button.

Dryer circuit

PartSize
Breaker30 A 2-pole (or as the nameplate lists)
Cable10/3 NM-B with ground
ReceptacleNEMA 14-30R
Ground10 AWG copper

NEC 220.54 counts at least 5,000 W per dryer in a load calculation. Three-wire 10/3 without ground (NEMA 10-30) is allowed only on existing circuits (250.140 Exception).

Long runs

WireAmpacity3% at 24 A
10 AWG30 A120 ft
8 AWG50 A192 ft
6 AWG65 A305 ft

Common questions

Can I use 10/2 for a dryer?

Not for new work. A 10/2 cable has only two insulated conductors plus ground; modern dryers need the neutral for the 120 V timer and motor.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)