Dryer wire size
Most electric dryers need a 30 A, 240 V circuit on 10 AWG copper. New installations use four wires: two hots, neutral and ground, ending in a NEMA 14-30 receptacle.
Dryer circuit
Fill in the circuit, then press the button.
Dryer circuit
| Part | Size |
|---|---|
| Breaker | 30 A 2-pole (or as the nameplate lists) |
| Cable | 10/3 NM-B with ground |
| Receptacle | NEMA 14-30R |
| Ground | 10 AWG copper |
NEC 220.54 counts at least 5,000 W per dryer in a load calculation. Three-wire 10/3 without ground (NEMA 10-30) is allowed only on existing circuits (250.140 Exception).
Long runs
| Wire | Ampacity | 3% at 24 A |
|---|---|---|
| 10 AWG | 30 A | 120 ft |
| 8 AWG | 50 A | 192 ft |
| 6 AWG | 65 A | 305 ft |
Common questions
Can I use 10/2 for a dryer?
Not for new work. A 10/2 cable has only two insulated conductors plus ground; modern dryers need the neutral for the 120 V timer and motor.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)