Ground wire size calculator

The equipment ground is sized from the breaker or fuse protecting the circuit, not from the circuit wires. If you upsized the hots for voltage drop, the ground grows in proportion.

A

Equipment ground

Fill in the circuit, then press the button.

Table 250.122

Breaker up toCopperAluminum
15 A14 AWG12 AWG
20 A12 AWG10 AWG
60 A10 AWG8 AWG
100 A8 AWG6 AWG
200 A6 AWG4 AWG
300 A4 AWG2 AWG
400 A3 AWG1 AWG
500 A2 AWG1/0 AWG
600 A1 AWG2/0 AWG
800 A1/0 AWG3/0 AWG
1000 A2/0 AWG4/0 AWG
1200 A3/0 AWG250 kcmil

Upsizing for voltage drop

If 6 AWG copper would carry the load but you install 4 AWG for distance, the area ratio is 41,740 รท 26,240 = 1.59. A 60 A circuit's 10 AWG ground (10,380 cmil) must grow to 16,510 cmil or more: 8 AWG.

Common questions

Is the ground wire the same as the neutral?

No. The neutral carries current in normal use. The ground carries current only during a fault, which is why it can be smaller.