Ground wire size calculator
The equipment ground is sized from the breaker or fuse protecting the circuit, not from the circuit wires. If you upsized the hots for voltage drop, the ground grows in proportion.
Equipment ground
Fill in the circuit, then press the button.
Table 250.122
| Breaker up to | Copper | Aluminum |
|---|---|---|
| 15 A | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 10 AWG |
| 60 A | 10 AWG | 8 AWG |
| 100 A | 8 AWG | 6 AWG |
| 200 A | 6 AWG | 4 AWG |
| 300 A | 4 AWG | 2 AWG |
| 400 A | 3 AWG | 1 AWG |
| 500 A | 2 AWG | 1/0 AWG |
| 600 A | 1 AWG | 2/0 AWG |
| 800 A | 1/0 AWG | 3/0 AWG |
| 1000 A | 2/0 AWG | 4/0 AWG |
| 1200 A | 3/0 AWG | 250 kcmil |
Upsizing for voltage drop
If 6 AWG copper would carry the load but you install 4 AWG for distance, the area ratio is 41,740 รท 26,240 = 1.59. A 60 A circuit's 10 AWG ground (10,380 cmil) must grow to 16,510 cmil or more: 8 AWG.
Common questions
Is the ground wire the same as the neutral?
No. The neutral carries current in normal use. The ground carries current only during a fault, which is why it can be smaller.