SER cable size
SER is four-conductor service entrance cable, usually aluminum, used for services and for feeders to ranges and subpanels. Indoors in thermal insulation it follows the 60 °C rule.
SER size
Fill in the circuit, then press the button.
Common SER sizes
| SER (aluminum) | 75 °C | 60 °C (interior, in insulation) | Typical use |
|---|---|---|---|
| 6 AWG | 50 A | 40 A | 40–50 A range |
| 4 AWG | 65 A | 55 A | 60 A subpanel |
| 2 AWG | 90 A | 75 A | 90 A subpanel |
| 1/0 AWG | 120 A | 100 A | 100–125 A feeder |
| 2/0 AWG | 135 A | 115 A | 150 A service (310.12) |
| 4/0 AWG | 180 A | 150 A | 200 A service (310.12) |
Table 310.16, aluminum. Under 338.10(B)(4), SE cable used for interior wiring follows Part II of Article 334, and where it runs through thermal insulation its ampacity is limited to the 60 °C column.
Where the 60 °C rule bites
A 100 A subpanel fed with 1/0 SER through an insulated wall is limited to 100 A (60 °C), which works. A 125 A feeder through insulation needs 2/0 SER. Exposed in a garage or in an uninsulated basement, the 75 °C rating applies.
Common questions
What size SER for a 100 amp subpanel?
1/0 aluminum SER is common: 120 A at 75 °C and 100 A at 60 °C. 2 AWG SER (90 A at 75 °C) is not enough for a 100 A feeder.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)