Voltage Drop Calculator

HomeCircuits

SER cable size

SER is four-conductor service entrance cable, usually aluminum, used for services and for feeders to ranges and subpanels. Indoors in thermal insulation it follows the 60 °C rule.

One way. Enter 0 to skip voltage drop.
V
%

SER size

Fill in the circuit, then press the button.

Common SER sizes

SER (aluminum)75 °C60 °C (interior, in insulation)Typical use
6 AWG50 A40 A40–50 A range
4 AWG65 A55 A60 A subpanel
2 AWG90 A75 A90 A subpanel
1/0 AWG120 A100 A100–125 A feeder
2/0 AWG135 A115 A150 A service (310.12)
4/0 AWG180 A150 A200 A service (310.12)

Table 310.16, aluminum. Under 338.10(B)(4), SE cable used for interior wiring follows Part II of Article 334, and where it runs through thermal insulation its ampacity is limited to the 60 °C column.

Where the 60 °C rule bites

A 100 A subpanel fed with 1/0 SER through an insulated wall is limited to 100 A (60 °C), which works. A 125 A feeder through insulation needs 2/0 SER. Exposed in a garage or in an uninsulated basement, the 75 °C rating applies.

Common questions

What size SER for a 100 amp subpanel?

1/0 aluminum SER is common: 120 A at 75 °C and 100 A at 60 °C. 2 AWG SER (90 A at 75 °C) is not enough for a 100 A feeder.