Underground wire size calculator
Runs to detached garages, shops and barns are long, so voltage drop usually decides the wire. Enter the feeder rating and the trench length.
Feeder size
Fill in the circuit, then press the button.
Feeder sizes by distance
| Load | 50 ft | 100 ft | 150 ft | 200 ft | 300 ft | 400 ft |
|---|---|---|---|---|---|---|
| 24 A | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 3 AWG | 2 AWG |
| 32 A | 8 AWG | 6 AWG | 4 AWG | 4 AWG | 2 AWG | 1 AWG |
| 48 A | 6 AWG | 4 AWG | 3 AWG | 2 AWG | 1/0 AWG | 2/0 AWG |
| 80 A | 2 AWG | 2 AWG | 1 AWG | 1/0 AWG | 3/0 AWG | 4/0 AWG |
Aluminum, 240 V, 3% drop. Loads are 80% of 30, 40, 60 and 100 A breakers. Copper is usually two sizes smaller.
What to run
- Direct burial: UF-B up to 6 AWG for small loads, or aluminum URD quadplex for larger feeders, 24 in deep.
- Conduit: PVC Schedule 40 at 18 in, with THWN-2 or XHHW-2 conductors. Use Schedule 80 where it rises above grade and may be damaged.
- Four wires for a feeder to a building: two hots, neutral and ground, plus a ground rod at the building.
Common questions
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Is aluminum OK underground?
Yes. URD and XHHW-2 aluminum is standard for underground feeders and services. Use lugs rated for aluminum and antioxidant compound where the lug maker calls for it.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)