Runs to detached garages, shops and barns are long, so voltage drop usually decides the wire. Enter the feeder rating and the trench length.

V
A
One way, from the source to the load.
%

Feeder size

Fill in the circuit, then press the button.

Feeder sizes by distance

Load50 ft100 ft150 ft200 ft300 ft400 ft
24 A10 AWG8 AWG6 AWG4 AWG3 AWG2 AWG
32 A8 AWG6 AWG4 AWG4 AWG2 AWG1 AWG
48 A6 AWG4 AWG3 AWG2 AWG1/0 AWG2/0 AWG
80 A2 AWG2 AWG1 AWG1/0 AWG3/0 AWG4/0 AWG

Aluminum, 240 V, 3% drop. Loads are 80% of 30, 40, 60 and 100 A breakers. Copper is usually two sizes smaller.

What to run

  • Direct burial: UF-B up to 6 AWG for small loads, or aluminum URD quadplex for larger feeders, 24 in deep.
  • Conduit: PVC Schedule 40 at 18 in, with THWN-2 or XHHW-2 conductors. Use Schedule 80 where it rises above grade and may be damaged.
  • Four wires for a feeder to a building: two hots, neutral and ground, plus a ground rod at the building.

Common questions

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Is aluminum OK underground?

Yes. URD and XHHW-2 aluminum is standard for underground feeders and services. Use lugs rated for aluminum and antioxidant compound where the lug maker calls for it.