Voltage Drop Calculator

HomeCircuits

27 kW tankless water heater wire size

A 27 kW electric tankless draws 112 A at 240 V. Most units split that across two to four circuits. Enter the kW for one circuit to size it.

V
One way from the panel. Enter 0 to skip voltage drop.
%

One heater circuit

Fill in the circuit, then press the button.

27 kW split across circuits

CircuitskW eachAmps eachBreaker each (125%)Copper each
213.556.2 A80 A4 AWG
39.037.5 A50 A8 AWG
46.828.1 A40 A8 AWG

Follow the unit's installation manual; it lists the exact number of circuits and the breaker for each. Tankless heaters are treated as continuous loads (422.13).

Can your service handle it?

112 A is a big share of a 200 A service. A load calculation under NEC 220.82 or 220.87 shows whether the service can take it, and many homes with 100 A or 150 A service cannot.

Common questions

What size breaker for a 27 kW tankless?

It depends on how many circuits the unit uses. As 3 equal circuits, each needs a 50 A breaker.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)