3,500 watt water heater wire size
A 3,500 W element at 240 V draws 14.6 A. Storage water heaters count as continuous loads under NEC 422.13, so the circuit is sized at 125%: 18.2 A.
Water heater circuit
Fill in the circuit, then press the button.
3,500 W water heater circuit
| Part | Size |
|---|---|
| Current | 14.6 A at 240 V, 16.8 A at 208 V |
| Minimum breaker | 20 A |
| Common breaker | 30 A |
| Copper | 10 AWG |
| Ground | 10 AWG |
Only one element heats at a time on standard dual-element tanks, so the nameplate wattage is the circuit load.
At 208 V
On a 208 V supply a 240 V element puts out only about 75% of its rated watts ((208 ÷ 240)²). Use elements rated for 208 V, or accept slower recovery.
Common questions
Can a 3500 W water heater go on a 20 A breaker?
No. 14.6 A × 125% = 18.2 A, which needs at least a 20 A breaker.