Voltage Drop Calculator

HomeCircuits

4,500 watt water heater wire size

A 4,500 W element at 240 V draws 18.8 A. Storage water heaters count as continuous loads under NEC 422.13, so the circuit is sized at 125%: 23.4 A.

V
One way from the panel. Enter 0 to skip voltage drop.
%

Water heater circuit

Fill in the circuit, then press the button.

4,500 W water heater circuit

PartSize
Current18.8 A at 240 V, 21.6 A at 208 V
Minimum breaker25 A
Common breaker30 A
Copper10 AWG
Ground10 AWG

Only one element heats at a time on standard dual-element tanks, so the nameplate wattage is the circuit load.

At 208 V

On a 208 V supply a 240 V element puts out only about 75% of its rated watts ((208 ÷ 240)²). Use elements rated for 208 V, or accept slower recovery.

Common questions

Can a 4500 W water heater go on a 20 A breaker?

No. 18.8 A × 125% = 23.4 A, which needs at least a 25 A breaker.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)