4,500 watt water heater wire size
A 4,500 W element at 240 V draws 18.8 A. Storage water heaters count as continuous loads under NEC 422.13, so the circuit is sized at 125%: 23.4 A.
Water heater circuit
Fill in the circuit, then press the button.
4,500 W water heater circuit
| Part | Size |
|---|---|
| Current | 18.8 A at 240 V, 21.6 A at 208 V |
| Minimum breaker | 25 A |
| Common breaker | 30 A |
| Copper | 10 AWG |
| Ground | 10 AWG |
Only one element heats at a time on standard dual-element tanks, so the nameplate wattage is the circuit load.
At 208 V
On a 208 V supply a 240 V element puts out only about 75% of its rated watts ((208 ÷ 240)²). Use elements rated for 208 V, or accept slower recovery.
Common questions
Can a 4500 W water heater go on a 20 A breaker?
No. 18.8 A × 125% = 23.4 A, which needs at least a 25 A breaker.