50 amp hot tub wire size

Spas list their required breaker on the label. A 50 A spa circuit needs 8 AWG copper at 75 °C, GFCI protection and a disconnect 5 to 50 ft from the tub.

V
One way from the panel. Enter 0 to skip voltage drop.
%

Spa circuit

Fill in the circuit, then press the button.

50 A spa circuit

PartSize
Breaker50 A GFCI
Copper THWN-2 (75 °C)8 AWG
Insulated copper ground10 AWG minimum, 12 AWG minimum (680.23(F)(2))
Disconnectwithin sight, at least 5 ft from the water (680.13)

Distance

WireAmpacity3% at 40 A
8 AWG50 A115 ft
6 AWG65 A183 ft
4 AWG85 A292 ft

Run the circuit in conduit with an insulated copper ground; NM cable is not allowed for the outdoor portion.

Common questions

Does a hot tub need a GFCI?

Yes. NEC 680.44 requires GFCI protection for outdoor spas and hot tubs, usually a GFCI breaker in the disconnect.