Baseboard heater wire size
Add the watts of every heater on the circuit. Fixed electric heat counts as continuous (424.4(B)), so the circuit is sized at 125%.
Heater circuit
Fill in the circuit, then press the button.
Maximum watts per circuit
| Breaker | Wire (Cu) | Max at 240 V | Max at 120 V |
|---|---|---|---|
| 15 A | 14 AWG | 2,880 W | 1,440 W |
| 20 A | 12 AWG | 3,840 W | 1,920 W |
| 30 A | 10 AWG | 5,760 W | 2,880 W |
Tips
- 240 V heaters draw half the current of 120 V models of the same watts.
- A line-voltage thermostat must be rated for the full circuit current.
Common questions
How many baseboard heaters on a 20 amp circuit?
Up to 3,840 W at 240 V, such as two 1,500 W heaters plus a 750 W unit.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)