5,500 watt water heater wire size
A 5,500 W element at 240 V draws 22.9 A. Storage water heaters count as continuous loads under NEC 422.13, so the circuit is sized at 125%: 28.6 A.
Water heater circuit
Fill in the circuit, then press the button.
5,500 W water heater circuit
| Part | Size |
|---|---|
| Current | 22.9 A at 240 V, 26.4 A at 208 V |
| Minimum breaker | 30 A |
| Common breaker | 30 A |
| Copper | 10 AWG |
| Ground | 10 AWG |
Only one element heats at a time on standard dual-element tanks, so the nameplate wattage is the circuit load.
At 208 V
On a 208 V supply a 240 V element puts out only about 75% of its rated watts ((208 ÷ 240)²). Use elements rated for 208 V, or accept slower recovery.
Common questions
Can a 5500 W water heater go on a 20 A breaker?
No. 22.9 A × 125% = 28.6 A, which needs at least a 30 A breaker.