1 HP well pump wire size
A 1 HP 230 V pump has a full-load current of 8 A in NEC Table 430.248. The real limit is usually length: the cable runs down the well, so check the total.
Pump circuit
Fill in the circuit, then press the button.
Maximum length for 1 HP at 230 V
| Cable | Length to motor |
|---|---|
| 14 AWG | 228 ft |
| 12 AWG | 363 ft |
| 10 AWG | 579 ft |
| 8 AWG | 923 ft |
| 6 AWG | 1,463 ft |
| 4 AWG | 2,333 ft |
5% drop at the NEC full-load current of 8 A. Pump makers publish their own charts based on service-factor amps, which are higher; use them where you can.
Length is from the pressure switch or control box to the motor: the horizontal run plus the pump setting depth.
Circuit
| Part | Size |
|---|---|
| Branch-circuit wire (125%) | 14 AWG |
| Maximum breaker (250%) | 20 A |
| Typical breaker | 20 A |
Use the control box or pump manual's breaker size when it gives one.
Common questions
How far can I run 12 gauge to a 1 HP pump?
About 363 ft at 230 V and 5% drop, based on the table current. Service-factor amps can cut that by 20% or more.