HomeCircuits

Heat Pump wire size

A heat pump outdoor unit is sized the same way as an AC condenser, from its MCA and MOCP. The air handler with backup heat strips is a separate circuit. Enter the MCA below.

V
One way from the panel. Enter 0 to skip voltage drop.
%

Unit circuit

Fill in the circuit, then press the button.

Reading the nameplate

MCA is the minimum ampacity of the wire, already including 125% of the compressor current. MOCP is the largest breaker allowed. Pick wire rated at or above MCA, and a breaker no larger than MOCP (440.22). The 240.4(D) small-conductor limits do not apply to these circuits (240.4(G)), so 12 AWG copper can serve an MCA up to 25 A. The breaker may be larger than the wire's ampacity here, because the compressor has its own overload protection.

Typical wire by MCA

MCACopper (75 °C)Common MOCP
12 A14 AWG20 A
15 A14 AWG25 A
18 A14 AWG30 A
22 A12 AWG35 A
28 A10 AWG45 A
34 A10 AWG50 A
40 A8 AWG60 A

The breaker shown is a common MOCP for that MCA; always use the value on your unit's label.

Common questions

Can I use 12 gauge wire with a 25 A breaker for an AC?

Yes, if the unit's MCA is 20 A or less and its MOCP allows 25 A. Article 440 allows the breaker to exceed the wire ampacity for hermetic compressors.

Sources