10 kW electric furnace wire size

10 kW at 240 V is 41.7 A. Fixed electric heat is sized at 125%, and heating elements over 48 A must be split into circuits of 48 A or less (424.22(B)).

V
One way from the panel. Enter 0 to skip voltage drop.
%

Furnace circuit

Fill in the circuit, then press the button.

10 kW furnace

CircuitskW eachAmpsBreaker (125%)Copper (75 °C)
110.041.7 A60 A6 AWG
25.020.8 A30 A10 AWG

Add the blower motor current from the nameplate if the unit lists a single MCA; most air handlers list MCA and MOCP for each circuit.

Common questions

What breaker does a 10 kW furnace need?

As 1 circuit, 60 A each. The unit label lists the MOCP for each circuit; use it.