18 kW tankless water heater wire size
A 18 kW electric tankless draws 75 A at 240 V. Most units split that across two to four circuits. Enter the kW for one circuit to size it.
One heater circuit
Fill in the circuit, then press the button.
18 kW split across circuits
| Circuits | kW each | Amps each | Breaker each (125%) | Copper each |
|---|---|---|---|---|
| 2 | 9.0 | 37.5 A | 50 A | 8 AWG |
| 3 | 6.0 | 25.0 A | 35 A | 8 AWG |
| 4 | 4.5 | 18.8 A | 25 A | 10 AWG |
Follow the unit's installation manual; it lists the exact number of circuits and the breaker for each. Tankless heaters are treated as continuous loads (422.13).
Can your service handle it?
75 A is a big share of a 200 A service. A load calculation under NEC 220.82 or 220.87 shows whether the service can take it, and many homes with 100 A or 150 A service cannot.
Common questions
What size breaker for a 18 kW tankless?
It depends on how many circuits the unit uses. As 2 equal circuits, each needs a 50 A breaker.