125 amp subpanel wire size
A 125 A subpanel feeder needs 1 AWG copper or 2/0 AWG aluminum at 75 °C, plus a ground. Detached garages and shops are often far enough away that voltage drop sets the size.
Feeder size
Fill in the circuit, then press the button.
125 A feeder
| Part | Copper | Aluminum |
|---|---|---|
| Hots and neutral | 1 AWG | 2/0 AWG |
| Equipment ground | 6 AWG | 4 AWG |
Table 310.16, 75 °C terminals, and Table 250.122.
A subpanel needs four wires: two hots, a neutral and a ground. In the subpanel the neutral bar is isolated from the enclosure and the ground bar is bonded to it. A detached building also needs its own grounding electrode (250.32).
Maximum distance at 3%, 100 A load, 240 V
| Copper | Ampacity | Max distance |
|---|---|---|
| 1 AWG | 130 A | 233 ft |
| 1/0 AWG | 150 A | 295 ft |
| 2/0 AWG | 175 A | 372 ft |
| 3/0 AWG | 200 A | 469 ft |
| Aluminum | Ampacity | Max distance |
|---|---|---|
| 2/0 AWG | 135 A | 226 ft |
| 3/0 AWG | 155 A | 285 ft |
| 4/0 AWG | 180 A | 360 ft |
| 250 kcmil | 205 A | 425 ft |
Based on 80% of the breaker rating, a realistic heavy load. If the panel will see lighter use, 5% total is still within NEC guidance.
Common questions
What size wire for a 125 amp subpanel 100 feet away?
At 100 ft, 3 AWG copper or 1 AWG aluminum keeps the drop under 3% at 100 A.
What size wire for a 125 amp subpanel 200 feet away?
At 200 ft, 1 AWG copper or 2/0 AWG aluminum keeps the drop under 3% at 100 A.
Can I feed a subpanel with 3 wires?
Not for new work. Since the 2008 NEC, feeders to detached buildings need a separate equipment ground (250.32(B)).