400 amp service wire size
A 400 A single-family service may use 400 kcmil copper or 600 kcmil aluminum under NEC 310.12. Long underground laterals and feeders that serve only part of the building need more.
Service conductors
Fill in the circuit, then press the button.
400 A conductor sizes
| Use | Copper | Aluminum | Basis |
|---|---|---|---|
| Whole-dwelling service or main feeder | 400 kcmil | 600 kcmil | Table 310.12 (83% of rating) |
| Feeder to part of the building | 600 kcmil | None AWG | Table 310.16, 75 °C |
| Grounding electrode conductor | 1/0 AWG | 3/0 AWG | Table 250.66, based on the aluminum size |
Table 310.12 lets a one-family dwelling service be sized at 83% of its rating because the whole house never draws its full rating for long. It applies only where the conductors carry the entire dwelling load, and only for 120/240 V single-phase services. Correction factors for heat, such as conductors in a hot attic or on a sunny roof, still apply.
Voltage drop on a 400 A service
At 83% of rating (332 A), single-phase 240 V:
| One-way length | 600 kcmil Al | 400 kcmil Cu |
|---|---|---|
| 50 ft | 1.2 V (0.5%) | 1.1 V (0.4%) |
| 100 ft | 2.3 V (1.0%) | 2.1 V (0.9%) |
| 150 ft | 3.5 V (1.5%) | 3.2 V (1.3%) |
| 200 ft | 4.7 V (2.0%) | 4.3 V (1.8%) |
| 300 ft | 7.0 V (2.9%) | 6.4 V (2.7%) |
Most utilities own the drop or lateral to the meter; this applies to conductors you install. Meter-to-house runs over about 150 ft often go one or two sizes larger.
Cable choices
- SER (4 conductors) or SEU (3 conductors) for overhead service entrance runs.
- URD / USE-2 aluminum triplex or quadruplex for direct-burial laterals, 24 in deep under Table 300.5.
- XHHW-2 or THWN-2 in conduit.
The neutral may be smaller than the hots when the calculated neutral load allows (220.61), but not smaller than the grounding electrode conductor (250.24(C)).
Common questions
Can I use 600 kcmil aluminum for a 400 amp service?
Yes, for a single-family dwelling service under 310.12. For a 400 A feeder that is not the main service, use None AWG aluminum.
Does 310.12 apply to a subpanel?
Only if that panel is fed by conductors carrying the entire dwelling load, such as a main disconnect outside feeding the interior panel. A garage or shop subpanel uses Table 310.16.