Wire size for 225 amps
A 225 amp circuit needs at least 4/0 AWG copper or 300 kcmil aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.
Wire size
Fill in the circuit, then press the button.
Minimum wire for 225 amps
| Conductor | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| Copper | 300 kcmil | 4/0 AWG | 3/0 AWG |
| Aluminum | 400 kcmil | 300 kcmil | 250 kcmil |
NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).
Most 225 A circuits land on 4/0 AWG copper or 300 kcmil aluminum, using the 75 °C column. If the cable is NM-B (Romex) or any terminal is rated only 60 °C, use 300 kcmil copper. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.
A 225 A service or main feeder for a single-family home may use the smaller sizes in Table 310.12: 3/0 AWG copper or 250 kcmil aluminum.
How far can a 225 amp circuit run?
Maximum one-way distance at 3% drop with the circuit loaded to 180 A (80% of the breaker). Past these lengths, use the next column.
| Voltage | 4/0 AWG | 250 kcmil | 300 kcmil | 350 kcmil | 400 kcmil |
|---|---|---|---|---|---|
| 240 V | 328 ft | 388 ft | 466 ft | 544 ft | 623 ft |
| 208 V 3φ | 329 ft | 388 ft | 466 ft | 545 ft | 623 ft |
| 480 V 3φ | 759 ft | 896 ft | 1,076 ft | 1,258 ft | 1,438 ft |
Copper. Three-phase rows use 1.732 in place of 2.
Other parts of a 225 A circuit
- Equipment ground: 4 AWG copper or 2 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
- Typical uses: upgraded services and feeders.
- Continuous loads: a 225 A breaker can carry 180 A continuously (210.19, 215.2).
Common questions
Can I use 4/0 AWG for 225 amps?
Yes, 4/0 AWG copper is rated 230 A at 75 °C, enough for a 225 A breaker as long as every termination is rated 75 °C and the run is short enough for voltage drop, about 328 ft at 240 V.
What size aluminum wire for 225 amps?
300 kcmil aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)