Wire size for 350 amps
A 350 amp circuit needs at least 500 kcmil copper or 750 kcmil aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.
Wire size
Fill in the circuit, then press the button.
Minimum wire for 350 amps
| Conductor | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| Copper | 600 kcmil | 500 kcmil | 350 kcmil |
| Aluminum | — | 750 kcmil | 500 kcmil |
NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).
Most 350 A circuits land on 500 kcmil copper or 750 kcmil aluminum, using the 75 °C column. If the cable is NM-B (Romex) or any terminal is rated only 60 °C, use 600 kcmil copper. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.
A 350 A service or main feeder for a single-family home may use the smaller sizes in Table 310.12: 350 kcmil copper or 500 kcmil aluminum.
How far can a 350 amp circuit run?
Maximum one-way distance at 3% drop with the circuit loaded to 280 A (80% of the breaker). Past these lengths, use the next column.
| Voltage | 500 kcmil | 600 kcmil | 750 kcmil |
|---|---|---|---|
| 240 V | 498 ft | 600 ft | 751 ft |
| 208 V 3φ | 498 ft | 601 ft | 752 ft |
| 480 V 3φ | 1,150 ft | 1,387 ft | 1,736 ft |
Copper. Three-phase rows use 1.732 in place of 2.
Other parts of a 350 A circuit
- Equipment ground: 3 AWG copper or 1 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
- Typical uses: commercial feeders and 400 A class services.
- Continuous loads: a 350 A breaker can carry 280 A continuously (210.19, 215.2).
Common questions
Can I use 500 kcmil for 350 amps?
Yes, 500 kcmil copper is rated 380 A at 75 °C, enough for a 350 A breaker as long as every termination is rated 75 °C and the run is short enough for voltage drop, about 498 ft at 240 V.
What size aluminum wire for 350 amps?
750 kcmil aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)