A 350 amp circuit needs at least 500 kcmil copper or 750 kcmil aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.

V
A
One way, from the source to the load.
%

Wire size

Fill in the circuit, then press the button.

Minimum wire for 350 amps

Conductor60 °C75 °C90 °C
Copper600 kcmil500 kcmil350 kcmil
Aluminum—750 kcmil500 kcmil

NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).

Most 350 A circuits land on 500 kcmil copper or 750 kcmil aluminum, using the 75 °C column. If the cable is NM-B (Romex) or any terminal is rated only 60 °C, use 600 kcmil copper. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.

A 350 A service or main feeder for a single-family home may use the smaller sizes in Table 310.12: 350 kcmil copper or 500 kcmil aluminum.

How far can a 350 amp circuit run?

Maximum one-way distance at 3% drop with the circuit loaded to 280 A (80% of the breaker). Past these lengths, use the next column.

Voltage500 kcmil600 kcmil750 kcmil
240 V498 ft600 ft751 ft
208 V 3φ498 ft601 ft752 ft
480 V 3φ1,150 ft1,387 ft1,736 ft

Copper. Three-phase rows use 1.732 in place of 2.

Other parts of a 350 A circuit

  • Equipment ground: 3 AWG copper or 1 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
  • Typical uses: commercial feeders and 400 A class services.
  • Continuous loads: a 350 A breaker can carry 280 A continuously (210.19, 215.2).

Common questions

Can I use 500 kcmil for 350 amps?

Yes, 500 kcmil copper is rated 380 A at 75 °C, enough for a 350 A breaker as long as every termination is rated 75 °C and the run is short enough for voltage drop, about 498 ft at 240 V.

What size aluminum wire for 350 amps?

750 kcmil aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.