Voltage Drop Calculator

HomeWire size

Wire size for 250 amps

A 250 amp circuit needs at least 250 kcmil copper or 350 kcmil aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.

V
A
One way, from the source to the load.
%

Wire size

Fill in the circuit, then press the button.

Minimum wire for 250 amps

Conductor60 °C75 °C90 °C
Copper350 kcmil250 kcmil4/0 AWG
Aluminum500 kcmil350 kcmil300 kcmil

NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).

Most 250 A circuits land on 250 kcmil copper or 350 kcmil aluminum, using the 75 °C column. If the cable is NM-B (Romex) or any terminal is rated only 60 °C, use 350 kcmil copper. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.

A 250 A service or main feeder for a single-family home may use the smaller sizes in Table 310.12: 4/0 AWG copper or 300 kcmil aluminum.

How far can a 250 amp circuit run?

Maximum one-way distance at 3% drop with the circuit loaded to 200 A (80% of the breaker). Past these lengths, use the next column.

Voltage250 kcmil300 kcmil350 kcmil400 kcmil500 kcmil
240 V349 ft419 ft490 ft560 ft697 ft
208 V 3φ349 ft419 ft490 ft561 ft698 ft
480 V 3φ807 ft968 ft1,132 ft1,294 ft1,611 ft

Copper. Three-phase rows use 1.732 in place of 2.

Other parts of a 250 A circuit

  • Equipment ground: 4 AWG copper or 2 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
  • Typical uses: services and commercial feeders.
  • Continuous loads: a 250 A breaker can carry 200 A continuously (210.19, 215.2).

Common questions

Can I use 250 kcmil for 250 amps?

Yes, 250 kcmil copper is rated 255 A at 75 °C, enough for a 250 A breaker as long as every termination is rated 75 °C and the run is short enough for voltage drop, about 349 ft at 240 V.

What size aluminum wire for 250 amps?

350 kcmil aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)