Wire size for 50 amps
A 50 amp circuit needs at least 8 AWG copper or 6 AWG aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.
Wire size
Fill in the circuit, then press the button.
Minimum wire for 50 amps
| Conductor | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| Copper | 6 AWG | 8 AWG | 8 AWG |
| Aluminum | 4 AWG | 6 AWG | 6 AWG |
NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).
Most 50 A circuits land on 8 AWG copper or 6 AWG aluminum, using the 75 °C column. If the cable is NM-B (Romex) or any terminal is rated only 60 °C, use 6 AWG copper. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.
How far can a 50 amp circuit run?
Maximum one-way distance at 3% drop with the circuit loaded to 40 A (80% of the breaker). Past these lengths, use the next column.
| Voltage | 8 AWG | 6 AWG | 4 AWG | 3 AWG | 2 AWG |
|---|---|---|---|---|---|
| 240 V | 115 ft | 183 ft | 292 ft | 367 ft | 463 ft |
| 208 V 3φ | 115 ft | 183 ft | 292 ft | 367 ft | 464 ft |
| 480 V 3φ | 267 ft | 423 ft | 674 ft | 848 ft | 1,071 ft |
Copper. Three-phase rows use 1.732 in place of 2.
Other parts of a 50 A circuit
- Equipment ground: 10 AWG copper or 8 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
- Typical uses: ranges, 40 A EV chargers, hot tubs and welders.
- Continuous loads: a 50 A breaker can carry 40 A continuously (210.19, 215.2).
Common questions
Can I use 8 AWG for 50 amps?
Yes, 8 AWG copper is rated 50 A at 75 °C, enough for a 50 A breaker as long as every termination is rated 75 °C and the run is short enough for voltage drop, about 115 ft at 240 V.
What size aluminum wire for 50 amps?
6 AWG aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.