Voltage Drop Calculator

HomeWire size

Wire size for 50 amps

A 50 amp circuit needs at least 8 AWG copper or 6 AWG aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.

V
A
One way, from the source to the load.
%

Wire size

Fill in the circuit, then press the button.

Minimum wire for 50 amps

Conductor60 °C75 °C90 °C
Copper6 AWG8 AWG8 AWG
Aluminum4 AWG6 AWG6 AWG

NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).

Most 50 A circuits land on 8 AWG copper or 6 AWG aluminum, using the 75 °C column. If the cable is NM-B (Romex) or any terminal is rated only 60 °C, use 6 AWG copper. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.

How far can a 50 amp circuit run?

Maximum one-way distance at 3% drop with the circuit loaded to 40 A (80% of the breaker). Past these lengths, use the next column.

Voltage8 AWG6 AWG4 AWG3 AWG2 AWG
240 V115 ft183 ft292 ft367 ft463 ft
208 V 3φ115 ft183 ft292 ft367 ft464 ft
480 V 3φ267 ft423 ft674 ft848 ft1,071 ft

Copper. Three-phase rows use 1.732 in place of 2.

Other parts of a 50 A circuit

  • Equipment ground: 10 AWG copper or 8 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
  • Typical uses: ranges, 40 A EV chargers, hot tubs and welders.
  • Continuous loads: a 50 A breaker can carry 40 A continuously (210.19, 215.2).

Common questions

Can I use 8 AWG for 50 amps?

Yes, 8 AWG copper is rated 50 A at 75 °C, enough for a 50 A breaker as long as every termination is rated 75 °C and the run is short enough for voltage drop, about 115 ft at 240 V.

What size aluminum wire for 50 amps?

6 AWG aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)