Voltage Drop Calculator

HomeWire size

Wire size for 30 amps

A 30 amp circuit needs at least 10 AWG copper or 8 AWG aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.

V
A
One way, from the source to the load.
%

Wire size

Fill in the circuit, then press the button.

Minimum wire for 30 amps

Conductor60 °C75 °C90 °C
Copper10 AWG10 AWG10 AWG
Aluminum8 AWG8 AWG8 AWG

NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).

Most 30 A circuits land on 10 AWG copper or 8 AWG aluminum, using the 75 °C column. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.

How far can a 30 amp circuit run?

Maximum one-way distance at 3% drop with the circuit loaded to 24 A (80% of the breaker). Past these lengths, use the next column.

Voltage10 AWG8 AWG6 AWG4 AWG3 AWG
120 V60 ft96 ft152 ft243 ft306 ft
240 V120 ft192 ft305 ft487 ft612 ft

Copper. Three-phase rows use 1.732 in place of 2.

Other parts of a 30 A circuit

  • Equipment ground: 10 AWG copper or 8 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
  • Typical uses: electric dryers, 4,500 W water heaters and small central air units.
  • Continuous loads: a 30 A breaker can carry 24 A continuously (210.19, 215.2).

Cable types for 30 A

CableSizeWhy
NM-B (Romex)10 AWG/2 or /360 °C rating applies (334.80)
UF-B (buried)10 AWG/2 or /360 °C rating applies (340.80)
THHN in conduit10 AWG75 °C terminals
MC cable10 AWGcheck the terminal rating

Common questions

Can I use 10 AWG for 30 amps?

Yes, 10 AWG copper is rated 30 A at 75 °C, enough for a 30 A breaker as long as every termination is rated 75 °C and the run is short enough for voltage drop, about 120 ft at 240 V.

What size aluminum wire for 30 amps?

8 AWG aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)