Wire size for 30 amps
A 30 amp circuit needs at least 10 AWG copper or 8 AWG aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.
Wire size
Fill in the circuit, then press the button.
Minimum wire for 30 amps
| Conductor | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| Copper | 10 AWG | 10 AWG | 10 AWG |
| Aluminum | 8 AWG | 8 AWG | 8 AWG |
NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).
Most 30 A circuits land on 10 AWG copper or 8 AWG aluminum, using the 75 °C column. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.
How far can a 30 amp circuit run?
Maximum one-way distance at 3% drop with the circuit loaded to 24 A (80% of the breaker). Past these lengths, use the next column.
| Voltage | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 3 AWG |
|---|---|---|---|---|---|
| 120 V | 60 ft | 96 ft | 152 ft | 243 ft | 306 ft |
| 240 V | 120 ft | 192 ft | 305 ft | 487 ft | 612 ft |
Copper. Three-phase rows use 1.732 in place of 2.
Other parts of a 30 A circuit
- Equipment ground: 10 AWG copper or 8 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
- Typical uses: electric dryers, 4,500 W water heaters and small central air units.
- Continuous loads: a 30 A breaker can carry 24 A continuously (210.19, 215.2).
Cable types for 30 A
| Cable | Size | Why |
|---|---|---|
| NM-B (Romex) | 10 AWG/2 or /3 | 60 °C rating applies (334.80) |
| UF-B (buried) | 10 AWG/2 or /3 | 60 °C rating applies (340.80) |
| THHN in conduit | 10 AWG | 75 °C terminals |
| MC cable | 10 AWG | check the terminal rating |
Common questions
Can I use 10 AWG for 30 amps?
Yes, 10 AWG copper is rated 30 A at 75 °C, enough for a 30 A breaker as long as every termination is rated 75 °C and the run is short enough for voltage drop, about 120 ft at 240 V.
What size aluminum wire for 30 amps?
8 AWG aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)