Voltage Drop Calculator

HomeWire size

Wire size for 15 amps

A 15 amp circuit needs at least 14 AWG copper or 12 AWG aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.

V
A
One way, from the source to the load.
%

Wire size

Fill in the circuit, then press the button.

Minimum wire for 15 amps

Conductor60 °C75 °C90 °C
Copper14 AWG14 AWG14 AWG
Aluminum12 AWG12 AWG12 AWG

NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).

Most 15 A circuits land on 14 AWG copper or 12 AWG aluminum, using the 75 °C column. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.

How far can a 15 amp circuit run?

Maximum one-way distance at 3% drop with the circuit loaded to 12 A (80% of the breaker). Past these lengths, use the next column.

Voltage14 AWG12 AWG10 AWG8 AWG6 AWG
120 V47 ft75 ft120 ft192 ft305 ft
240 V95 ft151 ft241 ft385 ft610 ft

Copper. Three-phase rows use 1.732 in place of 2.

Other parts of a 15 A circuit

  • Equipment ground: 14 AWG copper or 12 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
  • Typical uses: general lighting and bedroom or living-room receptacles.
  • Continuous loads: a 15 A breaker can carry 12 A continuously (210.19, 215.2).

Cable types for 15 A

CableSizeWhy
NM-B (Romex)14 AWG/2 or /360 °C rating applies (334.80)
UF-B (buried)14 AWG/2 or /360 °C rating applies (340.80)
THHN in conduit14 AWG75 °C terminals
MC cable14 AWGcheck the terminal rating

Common questions

Can I use 14 AWG for 15 amps?

Yes, 14 AWG copper is rated 15 A at 75 °C, enough for a 15 A breaker as long as every termination is rated 75 °C.

What size aluminum wire for 15 amps?

12 AWG aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)