Voltage Drop Calculator

HomeWire size

Wire size for 20 amps

A 20 amp circuit needs at least 12 AWG copper or 10 AWG aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.

V
A
One way, from the source to the load.
%

Wire size

Fill in the circuit, then press the button.

Minimum wire for 20 amps

Conductor60 °C75 °C90 °C
Copper12 AWG12 AWG12 AWG
Aluminum10 AWG10 AWG10 AWG

NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).

Most 20 A circuits land on 12 AWG copper or 10 AWG aluminum, using the 75 °C column. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.

How far can a 20 amp circuit run?

Maximum one-way distance at 3% drop with the circuit loaded to 16 A (80% of the breaker). Past these lengths, use the next column.

Voltage12 AWG10 AWG8 AWG6 AWG4 AWG
120 V56 ft90 ft144 ft229 ft365 ft
240 V113 ft181 ft289 ft458 ft730 ft

Copper. Three-phase rows use 1.732 in place of 2.

Other parts of a 20 A circuit

  • Equipment ground: 12 AWG copper or 10 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
  • Typical uses: kitchen countertop, bathroom, laundry and garage receptacles, and microwaves.
  • Continuous loads: a 20 A breaker can carry 16 A continuously (210.19, 215.2).

Cable types for 20 A

CableSizeWhy
NM-B (Romex)12 AWG/2 or /360 °C rating applies (334.80)
UF-B (buried)12 AWG/2 or /360 °C rating applies (340.80)
THHN in conduit12 AWG75 °C terminals
MC cable12 AWGcheck the terminal rating

Common questions

Can I use 12 AWG for 20 amps?

Yes, 12 AWG copper is rated 20 A at 75 °C, enough for a 20 A breaker as long as every termination is rated 75 °C.

What size aluminum wire for 20 amps?

10 AWG aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)