Wire size for 20 amps
A 20 amp circuit needs at least 12 AWG copper or 10 AWG aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.
Wire size
Fill in the circuit, then press the button.
Minimum wire for 20 amps
| Conductor | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| Copper | 12 AWG | 12 AWG | 12 AWG |
| Aluminum | 10 AWG | 10 AWG | 10 AWG |
NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).
Most 20 A circuits land on 12 AWG copper or 10 AWG aluminum, using the 75 °C column. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.
How far can a 20 amp circuit run?
Maximum one-way distance at 3% drop with the circuit loaded to 16 A (80% of the breaker). Past these lengths, use the next column.
| Voltage | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG |
|---|---|---|---|---|---|
| 120 V | 56 ft | 90 ft | 144 ft | 229 ft | 365 ft |
| 240 V | 113 ft | 181 ft | 289 ft | 458 ft | 730 ft |
Copper. Three-phase rows use 1.732 in place of 2.
Other parts of a 20 A circuit
- Equipment ground: 12 AWG copper or 10 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
- Typical uses: kitchen countertop, bathroom, laundry and garage receptacles, and microwaves.
- Continuous loads: a 20 A breaker can carry 16 A continuously (210.19, 215.2).
Cable types for 20 A
| Cable | Size | Why |
|---|---|---|
| NM-B (Romex) | 12 AWG/2 or /3 | 60 °C rating applies (334.80) |
| UF-B (buried) | 12 AWG/2 or /3 | 60 °C rating applies (340.80) |
| THHN in conduit | 12 AWG | 75 °C terminals |
| MC cable | 12 AWG | check the terminal rating |
Common questions
Can I use 12 AWG for 20 amps?
Yes, 12 AWG copper is rated 20 A at 75 °C, enough for a 20 A breaker as long as every termination is rated 75 °C.
What size aluminum wire for 20 amps?
10 AWG aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.