Wire size for 70 amps
A 70 amp circuit needs at least 4 AWG copper or 3 AWG aluminum at 75 °C. Long runs need more. Enter your distance and voltage to check.
Wire size
Fill in the circuit, then press the button.
Minimum wire for 70 amps
| Conductor | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| Copper | 4 AWG | 4 AWG | 6 AWG |
| Aluminum | 2 AWG | 3 AWG | 4 AWG |
NEC Table 310.16, not more than three current-carrying conductors, 30 °C ambient. 14, 12 and 10 AWG are capped by 240.4(D).
Most 70 A circuits land on 4 AWG copper or 3 AWG aluminum, using the 75 °C column. The 90 °C column is only a starting point for derating; the final ampacity cannot exceed the 75 °C value at the terminals.
How far can a 70 amp circuit run?
Maximum one-way distance at 3% drop with the circuit loaded to 56 A (80% of the breaker). Past these lengths, use the next column.
| Voltage | 4 AWG | 3 AWG | 2 AWG | 1 AWG | 1/0 AWG |
|---|---|---|---|---|---|
| 240 V | 208 ft | 262 ft | 331 ft | 417 ft | 526 ft |
| 208 V 3φ | 208 ft | 262 ft | 331 ft | 417 ft | 527 ft |
| 480 V 3φ | 482 ft | 605 ft | 765 ft | 964 ft | 1,216 ft |
Copper. Three-phase rows use 1.732 in place of 2.
Other parts of a 70 A circuit
- Equipment ground: 8 AWG copper or 6 AWG aluminum (Table 250.122). Upsize it in proportion if you upsize the circuit wires for voltage drop.
- Typical uses: subpanels and air handlers with electric heat strips.
- Continuous loads: a 70 A breaker can carry 56 A continuously (210.19, 215.2).
Common questions
Can I use 4 AWG for 70 amps?
Yes, 4 AWG copper is rated 85 A at 75 °C, enough for a 70 A breaker as long as every termination is rated 75 °C and the run is short enough for voltage drop, about 208 ft at 240 V.
What size aluminum wire for 70 amps?
3 AWG aluminum at 75 °C. Aluminum drops more voltage than copper, so check long runs.
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)