Acceptable voltage drop
How much voltage drop is acceptable depends on who is asking. Here are the limits from the codes and standards, then a calculator to check your circuit against them.
Your circuit
Fill in the circuit, then press the button.
Limits by code and standard
| Source | Branch circuit | Total | Status |
|---|---|---|---|
| NEC 210.19 / 215.2 informational notes | 3% | 5% feeder + branch | Advisory |
| NEC 647.4(D), sensitive electronics | 1.5% | 2.5% | Mandatory |
| NEC 695.7, fire pumps | 5% running at the motor | 15% while starting | Mandatory |
| ASHRAE 90.1, section 8.4.1 | — | 5% feeder + branch | Mandatory where adopted |
| Canada, CEC Rule 8-102 | 3% | 5% | Mandatory |
| UK, BS 7671 Appendix 4 | 3% lighting, 5% other | from the origin | Deemed to comply |
| Australia & NZ, AS/NZS 3000 3.6.2 | — | 5% from point of supply | Mandatory |
| Boats, ABYC E-11 | 3% critical, 10% other | — | Industry standard |
Why the limits matter
Motors draw more current as voltage falls, run hotter and lose torque; a 10% drop can cut starting torque by about 19%. Resistance heaters lose output with the square of voltage, so 5% low means about 10% less heat. Electronics and LED drivers may reset or flicker. And the lost voltage is energy paid for and turned into heat in the walls.
Volts allowed by system voltage
| System | 1.5% | 3% | 5% | 10% |
|---|---|---|---|---|
| 12 V | 0.18 V | 0.36 V | 0.60 V | 1.20 V |
| 24 V | 0.36 V | 0.72 V | 1.20 V | 2.40 V |
| 48 V | 0.72 V | 1.44 V | 2.40 V | 4.80 V |
| 120 V | 1.80 V | 3.60 V | 6.00 V | 12.00 V |
| 208 V | 3.12 V | 6.24 V | 10.40 V | 20.80 V |
| 230 V | 3.45 V | 6.90 V | 11.50 V | 23.00 V |
| 240 V | 3.60 V | 7.20 V | 12.00 V | 24.00 V |
| 277 V | 4.16 V | 8.31 V | 13.85 V | 27.70 V |
| 480 V | 7.20 V | 14.40 V | 24.00 V | 48.00 V |
Common questions
Is 3% voltage drop a code requirement?
Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.
Is 5% voltage drop acceptable?
5% total from the service to the last outlet is the NEC's suggested ceiling, and the hard limit in Canada, Australia and buildings that follow ASHRAE 90.1. On a single branch circuit, 5% leaves no room for the feeder upstream.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
- CSA C22.1:24 Canadian Electrical Code, Part I, Rule 8-102
- BS 7671:2018+A2:2022, Appendix 4 (https://electrical.theiet.org/bs-7671/)
- AS/NZS 3000:2018 Electrical installations (Wiring Rules), clause 3.6.2
- ABYC E-11, AC and DC Electrical Systems on Boats (https://abycinc.org/)