How much voltage drop is acceptable depends on who is asking. Here are the limits from the codes and standards, then a calculator to check your circuit against them.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Your circuit

Fill in the circuit, then press the button.

Limits by code and standard

SourceBranch circuitTotalStatus
NEC 210.19 / 215.2 informational notes3%5% feeder + branchAdvisory
NEC 647.4(D), sensitive electronics1.5%2.5%Mandatory
NEC 695.7, fire pumps5% running at the motor15% while startingMandatory
ASHRAE 90.1, section 8.4.1—5% feeder + branchMandatory where adopted
Canada, CEC Rule 8-1023%5%Mandatory
UK, BS 7671 Appendix 43% lighting, 5% otherfrom the originDeemed to comply
Australia & NZ, AS/NZS 3000 3.6.2—5% from point of supplyMandatory
Boats, ABYC E-113% critical, 10% other—Industry standard

Why the limits matter

Motors draw more current as voltage falls, run hotter and lose torque; a 10% drop can cut starting torque by about 19%. Resistance heaters lose output with the square of voltage, so 5% low means about 10% less heat. Electronics and LED drivers may reset or flicker. And the lost voltage is energy paid for and turned into heat in the walls.

Volts allowed by system voltage

System1.5%3%5%10%
12 V0.18 V0.36 V0.60 V1.20 V
24 V0.36 V0.72 V1.20 V2.40 V
48 V0.72 V1.44 V2.40 V4.80 V
120 V1.80 V3.60 V6.00 V12.00 V
208 V3.12 V6.24 V10.40 V20.80 V
230 V3.45 V6.90 V11.50 V23.00 V
240 V3.60 V7.20 V12.00 V24.00 V
277 V4.16 V8.31 V13.85 V27.70 V
480 V7.20 V14.40 V24.00 V48.00 V

Common questions

Is 3% voltage drop a code requirement?

Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.

Is 5% voltage drop acceptable?

5% total from the service to the last outlet is the NEC's suggested ceiling, and the hard limit in Canada, Australia and buildings that follow ASHRAE 90.1. On a single branch circuit, 5% leaves no room for the feeder upstream.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
  • CSA C22.1:24 Canadian Electrical Code, Part I, Rule 8-102
  • BS 7671:2018+A2:2022, Appendix 4 (https://electrical.theiet.org/bs-7671/)
  • AS/NZS 3000:2018 Electrical installations (Wiring Rules), clause 3.6.2
  • ABYC E-11, AC and DC Electrical Systems on Boats (https://abycinc.org/)