Three-phase voltage drop calculator
For balanced three-phase loads such as motors, rooftop units and feeders. The three phases share the return path, so the drop uses √3 (1.732) instead of 2.
Voltage drop
Fill in the circuit, then press the button.
Three-phase formula
VD = 1.732 × R × L × I ÷ 1,000
R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.
Worked example
A 65 A motor feeder on 4 AWG copper, 300 ft at 480 V. VD = 1.732 × 0.308 × 300 × 65 ÷ 1,000 = 10.4 V, or 2.17%. The same run at 208 V would be 5.0%, which is why large loads move to 480 V.
Maximum distance at 3%, 480 V three-phase
| Load | 8 AWG | 6 AWG | 4 AWG | 2 AWG | 1/0 AWG | 3/0 AWG |
|---|---|---|---|---|---|---|
| 20 A | 534 ft | 846 ft | 1,349 ft | 2,142 ft | 3,407 ft | 5,426 ft |
| 40 A | 267 ft | 423 ft | 674 ft | 1,071 ft | 1,703 ft | 2,713 ft |
| 60 A | — | 282 ft | 449 ft | 714 ft | 1,135 ft | 1,808 ft |
| 100 A | — | — | — | 428 ft | 681 ft | 1,085 ft |
| 150 A | — | — | — | — | 454 ft | 723 ft |
| 200 A | — | — | — | — | — | 542 ft |
Maximum distance at 3%, 208 V three-phase
| Load | 8 AWG | 6 AWG | 4 AWG | 2 AWG | 1/0 AWG |
|---|---|---|---|---|---|
| 20 A | 231 ft | 366 ft | 584 ft | 928 ft | 1,476 ft |
| 40 A | 115 ft | 183 ft | 292 ft | 464 ft | 738 ft |
| 60 A | — | 122 ft | 194 ft | 309 ft | 492 ft |
| 100 A | — | — | — | 185 ft | 295 ft |
| 150 A | — | — | — | — | 196 ft |
The voltage is line to line. Use line-to-line voltage in the calculator for three-phase circuits.
Common questions
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Why 1.732 instead of 2?
In a balanced three-phase circuit the currents in the three lines are 120° apart and cancel at the neutral point, so the line-to-line drop is √3 times the drop in one conductor rather than twice it.
Does this work for unbalanced loads?
Use the current of the most heavily loaded phase for a conservative result. Severely unbalanced feeders with large neutral current need a per-phase calculation.