Three-phase voltage drop calculator

For balanced three-phase loads such as motors, rooftop units and feeders. The three phases share the return path, so the drop uses √3 (1.732) instead of 2.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Voltage drop

Fill in the circuit, then press the button.

Three-phase formula

VD = 1.732 × R × L × I ÷ 1,000

R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.

Worked example

A 65 A motor feeder on 4 AWG copper, 300 ft at 480 V. VD = 1.732 × 0.308 × 300 × 65 ÷ 1,000 = 10.4 V, or 2.17%. The same run at 208 V would be 5.0%, which is why large loads move to 480 V.

Maximum distance at 3%, 480 V three-phase

Load8 AWG6 AWG4 AWG2 AWG1/0 AWG3/0 AWG
20 A534 ft846 ft1,349 ft2,142 ft3,407 ft5,426 ft
40 A267 ft423 ft674 ft1,071 ft1,703 ft2,713 ft
60 A—282 ft449 ft714 ft1,135 ft1,808 ft
100 A———428 ft681 ft1,085 ft
150 A————454 ft723 ft
200 A—————542 ft

Maximum distance at 3%, 208 V three-phase

Load8 AWG6 AWG4 AWG2 AWG1/0 AWG
20 A231 ft366 ft584 ft928 ft1,476 ft
40 A115 ft183 ft292 ft464 ft738 ft
60 A—122 ft194 ft309 ft492 ft
100 A———185 ft295 ft
150 A————196 ft

The voltage is line to line. Use line-to-line voltage in the calculator for three-phase circuits.

Common questions

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Why 1.732 instead of 2?

In a balanced three-phase circuit the currents in the three lines are 120° apart and cancel at the neutral point, so the line-to-line drop is √3 times the drop in one conductor rather than twice it.

Does this work for unbalanced loads?

Use the current of the most heavily loaded phase for a conservative result. Severely unbalanced feeders with large neutral current need a per-phase calculation.