How to calculate voltage drop

Five steps, three worked examples, and a calculator below that does the same arithmetic so you can check each one.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Check your work

Fill in the circuit, then press the button.

The five steps

  1. Find the load current in amps from the nameplate, or watts ÷ volts.
  2. Measure the one-way length from the panel to the load along the actual route.
  3. Look up the wire's resistance per 1,000 ft in NEC Chapter 9, Table 8.
  4. Multiply 2 × R × L × I and divide by 1,000 (use 1.732 for three-phase).
  5. Divide the result by the source voltage and multiply by 100 for percent.

Example 1: garage receptacle

15 A on 12 AWG copper, 90 ft at 120 V. 2 × 1.98 × 90 × 15 ÷ 1,000 = 5.35 V, which is 4.5%. Too high for a 3% target. 10 AWG gives 3.35 V, 2.8%.

Example 2: well pump

A 1.5 HP, 230 V pump drawing 10 A on 12 AWG, 250 ft down the well and across the yard. 2 × 1.98 × 250 × 10 ÷ 1,000 = 9.9 V, 4.3%. Pump makers usually allow up to 5% on the motor leads, so this passes with little margin.

Example 3: 480 V motor feeder

65 A three-phase on 4 AWG, 300 ft. 1.732 × 0.308 × 300 × 65 ÷ 1,000 = 10.4 V, 2.2%.

Common mistakes

  • Using the round-trip length and then doubling it again.
  • Using the breaker rating instead of the actual load current. The breaker gives a worst case.
  • Forgetting that aluminum drops about 1.6 times as much as copper of the same gauge.
  • Using 2 instead of 1.732 on three-phase, which overstates the drop by 15%.

Common questions

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Should I use the breaker size or the load?

Use the expected load for a realistic figure. Use the breaker rating if you want a worst case or the load is unknown. Many engineers size feeders to keep drop under 3% at 80% of the breaker rating.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
  • https://www.southwire.com/calculator-vdrop